TECHNICAL ARTICLES

In a production line, an unstable sensor reading, an intermittent communication failure, or an incorrect inverter command can all have the same origin: electromagnetic interference in the cabling system. Therefore, the decision between shielded versus unshielded cable should not be based solely on cost per meter. It needs to consider the electrical behavior of the installation, the industrial environment, and the consequences of a potential failure.
Unshielded cables efficiently serve a variety of applications. However, when installed near sources of electrical noise, they can carry degraded signals and compromise the reliability of automation, instrumentation, and control systems. Shielding is an engineering feature to control this risk, but it only yields results when the cable, installation, and grounding are specified as a whole.
Shielded versus unshielded cable: what changes?
The key difference lies in the presence of a conductive layer around the conductors or inner pairs. This layer, typically made of metallic tape, copper braid, or a combination of both, acts as a barrier against electromagnetic and radio frequency interference. Depending on its construction, it also reduces the coupling of noise generated by the cable itself on nearby circuits.
In unshielded cable, the conductors are protected by insulation and an outer covering, but there is no specific barrier to control external interference. This does not mean low quality or technical inadequacy. It means that its application must occur under conditions compatible with the sensitivity of the circuit and the noise level of the environment.
In industrial installations, the comparison cannot be limited to "shielded cable is better." A shielded cable tends to have a higher cost, weight, and diameter. It also requires attention to the termination. If the shielding is interrupted, incorrectly grounded, or connected by a long conductor section, the protection intended in the design can be significantly reduced.
Armor plating is no substitute for proper construction.
Shielding controls interference, but it doesn't solve all the stresses of an application. Temperature, abrasion, oil, humidity, chemical agents, continuous bending, torsion, and traction all require compatible materials and geometries. A cable for a cable carrier , for example, demands specific mechanical performance, regardless of whether it is shielded or not.
Similarly, instrumentation cables may require twisted pairs to reduce susceptibility to noise. In low-intensity signal circuits, the combination of twisted pair and individual or collective shielding can be crucial for preserving measurement integrity. The correct solution depends on the signal type, circuit distance, and electromagnetic severity of the route.
When unshielded cable is the right choice
Unshielded cables are recommended when the circuit is not highly sensitive to noise and when the installation route is far from significant sources of interference. Conventional power supply circuits, lighting, simple controls, and applications with low electromagnetic compatibility requirements can operate adequately with this construction, provided that the criteria for cross-section, voltage, temperature, and installation are respected.
It can also be a suitable technical and economic choice in organized panels, with physical segregation between power cables and signal cables. The distance between circuits, the use of separate cable trays, and crossings at an angle close to 90 degrees help to reduce inductive and capacitive coupling. In these cases, the installation architecture contributes to ensuring that the absence of shielding does not represent an operational risk.
There are also situations where unshielded cable is preferable due to the required flexibility or available space. The point is not to turn initial savings into maintenance costs. If the environment has high noise levels or if the signal is critical for the safety, quality, or availability of the plant, reducing the specification without a technical analysis can lead to downtime and lengthy diagnoses.
When shielding becomes necessary
Shielding is gaining importance in instrumentation circuits, industrial networks, analog signals, encoders, servomotors, frequency inverters, and automation systems that share space with power loads. Motors driven by inverters, contactors, transformers, rectifiers, electric welding, and electronic switches are recurring sources of electromagnetic interference.
In a 4 to 20 mA circuit, for example, small disturbances can generate inconsistent readings, false alarms, or loss of stability in process control. In industrial communication, the effect can appear as packet errors, loss of synchronization, dropped connections, or intermittent behavior that is difficult to reproduce. In servo drive applications, adequate shielding also contributes to reducing emissions and preserving the quality of feedback signals.
The choice of shielding should consider its coverage and purpose. Metallic braid offers good mechanical and electrical coverage, with relevant performance in frequency ranges common in industrial applications. Metallic tape can extend coverage against interference, while combined constructions meet more demanding scenarios. For instrumentation pairs, individual shielding reduces interference between the pairs themselves; collective shielding protects the assembly against external noise.
Frequency inverters require specific analysis.
The cable between the inverter and the motor is subject to high-frequency pulses, high dv/dt values, and eddy currents. Using an inadequate construction can increase electromagnetic emissions, affect nearby equipment, and reduce the predictability of the installation. In this application, shielding must be considered along with insulation, thermal capacity, flexibility, rated voltage, and compatibility with the grounding method.
It is not enough to select a cable commercially identified as shielded. It is necessary to verify if it was designed for drives with frequency inverters and if its construction meets the real conditions of length, power, duty cycle and environment. In critical projects, the cable's technical documentation and the system's regulatory requirements should guide the decision.
The termination defines the shielding performance.
Even a well-designed shield can lose efficiency due to improper termination. Ideally, electrical continuity should be maintained along the path, and a low-impedance connection should be made at the point specified in the design. Connections using long pigtails, that is, a section of wire connecting the shield to ground, increase impedance at high frequencies and reduce noise control capacity.
Appropriate metal cable glands, connectors with shielded continuity, and 360-degree peripheral contact are frequent alternatives to preserve the performance of the assembly. The decision to ground at one or both ends depends on the type of circuit, the frequency involved, and the risk of circulating currents due to potential differences. There is no single rule applicable to all systems.
In low-frequency analog signals, grounding at one end may be adopted to avoid ground loops, according to the design philosophy. However, in high-frequency applications, such as inverters and certain communication systems, connection at both ends may be necessary for effective shielding. This criterion should be defined by the installation engineering, not by mounting convenience.
How to specify without transferring risk to the field
The specification should begin with the circuit and the environment, not the generic cable name. To make a consistent decision, the technical team needs to evaluate four aspects: signal characteristics, nearby interference sources, installation path, and mechanical and environmental requirements.
Characteristics such as voltage, current, frequency, impedance, signal sensitivity, and transmission distance indicate the level of protection required. Next, it is necessary to map motors, inverters, power busbars, welding equipment, and other emitters present along the route. Physical segregation can reduce the need for shielding in some sections, but it does not eliminate the need for electromagnetic compatibility analysis.
Finally, application requirements come into play: bending, twisting, sun exposure, flame, oil, water, corrosive atmosphere, marine installation, or operation in a harsh industrial area. A shielded cable for fixed use may not withstand continuous cycles on a conveyor belt. A flexible cable without suitable materials may fail under oil or high temperatures. The solution must combine electrical, mechanical, and environmental performance.
Innovcable develops special cables based on this engineering logic, evaluating the application to define construction, materials, and performance requirements compatible with the project. In fault-tolerant operations, the cable should not be treated as an isolated purchase item, but as an active part of the system's reliability.
The best choice isn't automatically the most protected cable, but rather the one that accurately meets the installation's demanding requirements. When noise, safety, and operational continuity are at stake, specifying correctly before installation is always more efficient than correcting faults after operation has stopped.
Shielded cable versus unshielded cable: which one to choose?
Related Articles

Everything about concentric cable: standards and applications.
Concentric Cable: A Complete Technical Guide for Engineers and Installers. Concentric cable represents an advanced engineering solution for networks.

Trends in Industrial Cables for 2026
Trends in industrial cabling combine automation, data, safety, and durability. Learn how to specify solutions for critical field environments.

Cable selection for frequency inverter
Selecting the right cable for your inverter reduces faults, noise, and downtime. Learn about the electrical, construction, and regulatory criteria for a safe specification.

Critical Safety: When to Specify a High-Performance vs. Conventional Fire Cable
In life safety systems, such as fire detection and alarm systems, the cable specification
Knowledge Academy: Technical information, standards and applications

Tables and Codes for Thermocouples
International Color Code for Compensation and Extension Cables and Wires - Cable Code - Error Limit Table

NBR 5410 Sizing Tables
DOWNLOAD NBR 5410 DIMENSIONING TABLES Explanation With the aim of offering a practical tool to assist in the work of

Color code tables
Color code according to DIN 47100 No. Colour Short Form 1 WHITE WH 2 BROWN BN 3

TABLE AND GUIDELINES AWG X METRIC CONVERSION (mm²)
Unveiling the AWG Standard: A Technical Guide for Professionals and Enthusiasts – American Wire Gauge (AWG) to Metric (mm²) Conversion
Questions? Send a message to the expert.
Access to cutting-edge scientific information is the fuel for innovation. These are the databases, journals, and repositories that our R&D team uses to stay at the forefront of global technical and scientific knowledge.
Databases, Repositories and Search Engines:
- IEEE Xplore Digital Library: The most crucial digital library for electrical and computer engineering. IEEE
- ACM Digital Library: A reference for the field of computer science and information technology. ACM
- Science Direct: Extensive collection of scientific publications and books from the publisher Elsevier. SCIENCE DIRECT
- Scopus: The largest database of abstracts and citations from peer-reviewed literature. scopus
- CAPES Journal Portal: It provides access to international scientific output for the teaching and research community in Brazil. CAPES
- Google Scholar Search tool focused on academic literature. GOOGLE SCHOLAR
- Brazilian Digital Library of Theses and Dissertations (BDTD): Repository of scientific output from Brazilian teaching and research institutions. BDTD
- Directory of Open Access Journals (DOAJ): A directory of high-quality open access journals. DOAJ
Prominent Scientific Periodicals and Journals:
- Naval, Offshore and Petroleum Engineering:
- Ocean Engineering (Elsevier)
- Journal of Ship Research (SNAME)
- Journal of Petroleum Science and Engineering (Elsevier)
- Journal of Marine Science and Engineering (MDPI)
- Journal of the Brazilian Society of Naval Engineering (SOBENA)
- Electrical, Electronic and Telecommunications Engineering:
Products

Profibus DP DeepSea® Armed SHF2
Busbar cable; PROFIBUS DP; Fixed installation; Nominal characteristic impedance: 150 Ω; 1x2x0,64; SHF2; Flame retardant: IEC 60332-1-2; violet; 8 mm

MariTimus® Single-Core Marine Power and Control Cable 0,6/1 kV XLPE/SHF1 (LSOH) Armored and Flame Retardant
Maritimus® Single-Core Naval Power and Control Cable; Armored; Max. 300,00 mm²; 0,6/1 kV; 1 conductor; XLPE / SHF1; Flame Retardant; +90°C; IEC 60092

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Fire Resistant IEC 60331
Maritimus® Single-Core Marine Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Armored and Fire Resistant IEC 60331
Maritimus® Armored Multicore Naval Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331