In this guide, you will find tables that decode the main classes.
  • Classes 1 and 2: Solid or stranded conductors, for fixed installations.
  • Classes 5 and 6: Flexible and extra-flexible conductors, for mobile equipment or applications requiring constant bending.

The following tables detail the specifications (number of wires and maximum resistance) according to the standards. IEC 60228, NM 280 (Mercosur) BS 6360 e VDE 0295, which are harmonized with each other. It shows the maximum diameter of the string; there may be fewer filaments, provided the maximum ohms/km is not exceeded.
Ohms Ω / km: shows the maximum permissible resistance for bare copper conductors in the indicated classes.

 

 Area mm² Class 1 Training
 Class 2 Training
 Ohms  Ω/km
 Class 5 Training
 Class 6 Training
 Ohms  Ω/km
0.1418 x 0.1018 x 0.10138.0
0.2514 x 0.1632 x 0.1079.0
0.3419 x 0.1642 x 0.1057.0
0.51 x 0.807 x 0.3036.016 x 0.2128 x 0.1039.0
0.751 x 0.977 x 0.37
24.524 x 0.2142 x 0.1626.0
1.01 x 1.137 x 0.4318.132 x 0.2156 x 0.1619.5
1.51 x 1.387 x 0.5312.130 x 0.2684 x 0.1613.3
2.51 x 1.787 x 0.677.4150 x 0.26140 x 0.167.98
4.01 x 2.267 x 0.854.6156 x 0.31224 x 0.164.95
6.01 x 2.767 x 1.043.0884 x 0.31192 x 0.213.30
10.01 x 3.577 x 1.351.8380 x 0.41320 x 0.211.91
16.01 x 4.517 x 1.701.15128 x 0.41512 x 0.211.21
25.07 x 2.140.72200 x 0.41800 x 0.210.78
35.07 x 2.520.524280 x 0.411120 x 0.210.554
50.019 x 1.780.387400 x 0.41705 x 0.310.386
70.019 x 2.140.268356 x 0.51990 x 0.310.272
95.019 x 2.520.193485 x 0.511340 x 0.310.206
12037 x 2.030.153614 x 0.511690 x 0.310.161
15037 x 2.250.124765 x 0.512123 x 0.310.129
18537 x 2.520.099944 x 0.511470 x 0.410.106
24061 x 2.250.0741225 x 0.51905 x 0.410.081
30061 x 2.520.060
40061 x 2.850.046
50061 x 3.200.036

Conductor class according to BS6360, IEC 60228, NM280 & VDE 0295

Related Articles

STANDARD

British cable standards BS4737-3.30:1986 Intrusion alarm systems. Specification for PVC insulated cables for interconnect wiring.

Read more "

Questions? Send a message to the specialist.

Products

Profibus DP Black double shielded cable, SHF2 DeepSea crossbar
Instrumentation cables - flame retardant SHF2

Profibus DP DeepSea® Armed SHF2

Busbar cable; PROFIBUS DP; Fixed installation; Nominal characteristic impedance: 150 Ω; 1x2x0,64; SHF2; Flame retardant: IEC 60332-1-2; violet; 8 mm

Read more "