Table 4F1A Flexible, thermosetting insulated cables with sheath, unshielded – IEEE

  • Table 4F1A

  • Flexible, insulated, thermosetting cables (heat-treated at 60°C) with shielding, unarmored.

  • Current Capacity (amperes):

  • Room Temperature: 30°C

  • Conductor Operating Temperature: 60°C

Current carrying capacity (amperes):

Ambient temperature: 30°C Conductor operating temperature: 60°C

Cross-sectional area of ​​the conductorSingle-phase AC or DCThree-phase AC.Single-phase AC or DC
1 double-core cable, with or without a protective conductor.1. Three nuclei, four nuclei, or five nuclei2 single-core cables
1234
(mm2)(A)(A)(A)
43026
63934
105147
167363
259783
35 102140
50 124175
70 158216
95 192258

Notes:

The tabulated rated currents are for cables in open air, but can also be used for cables supported on a surface. If the cable is wound on a drum under load, the rated currents should be reduced according to Note 2 below, and for cables that can be covered, Note 3 below.
Flexible cables wound on winding drums. The rated currents of cables used on winding drums should be reduced by the following factors: a) Radial drum b) Vented cylindrical drum Vented: 85% 1 cable layer: 85% Non-vented: 75% 2 cable layers: 65% 3 cable layers: 45% 4 cable layers: 35% A radial drum is one in which spiral layers of cable are accommodated between widely spaced flanges; if fitted with solid flanges, the rated currents given above should be reduced and the drum is described as non-vented. If the flanges have adequate openings, the drum is described as ventilated. A ventilated cylindrical drum for cables is one in which cable layers are accommodated between widely spaced flanges and the drum and end flanges have adequate ventilation openings.
When the cable can be covered or wound during loading, or air movement over the cable can be restricted, the rated current must be reduced. It is not possible to specify the reduction amount, but the rating factor table for winding drums can be used as a reference.

Table 4F1B Flexible Insulated Thermally Strengthened Cables 60°C – IEEE

  • Table 4F1B

  • Flexible, insulated, heat-set cables at 60°C.

  • Voltage Drop (in ampere-meters):

  • Conductor Operating Temperature: 60°C

Cross-sectional area of ​​the conductordual-core DC cableDual-core cable, single-phase alternating current.1 cable with three, four or five cores, three-phase alternating current.2 single-core cables in contact
DCsingle-phase AC*
123456
(mm2)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)
4121210
67.87.86.7
104.64.64.0
162.92.92.5
rxzrxzrxz
251.801.800.1751.851.550.1501.55
35 1.100.1501.151.311.310.211.32
50 0.830.1450.840.910.910.210.93
70 0.570.1400.580.640.640.200.67
95 0.420.1350.440.490.490.1950.53

Note: * A greater voltage drop will occur if the cables are spaced further apart.

Table 4F2A Flexible insulated thermosetting cables for 90°C and 180°C, sheathed, unarmored (copper conductors) – IEEE

  • Table 4F2A
  • Flexible, insulated, thermosetting cables (90°C and 180°C) with shielding, unarmored (copper conductors)
  • Driving ability
  • Current (amperes):
    Room Temperature: 30°C
  • Conductor operating temperature: 90°C
Conductor
cross-sectional 

area
Single-phase
ac or dc
Three-phase 
ac
Single-phase
ac or dc
1 two-core cable,
with or without protective conductor
1 three-core,
four-core or
five-core
2 single-core cables, touching
1234
(mm2)(A)(A)(A)
44237
65549
107666
1610389
25136119
35 146200
50 146200
50 177250
70 225310
95 273369
120 316432
150 363497
185 414567
240 487673
300 560773
400 924
500 1,062
630 1,242

Classification factor for ambient temperature

Thermoplastic or thermosetting insulated cables rated for 90°C:

Room temperature:35°C40°C45°C50°C55°C60°C65°C70°C75°C80°C85°C
Correction Factor:0.950.910.860.820.760.700.640.570.500.400.28

180°C thermosetting insulated cables:

Room temperature:35°C to 90°C95°C100°C105°C110°C150°C120°C125°C130°C135°C
Correction Factor:1.00.960.910.860.810.760.700.640.570.50
Room temperature:140°C145°C
Correction Factor:0.400.28

Remarks:

The tabulated rated currents are for cables in open air, but can also be used for cables supported on a surface. If the cable is wound on a drum under load, the rated currents should be reduced according to Note 2 below, and for cables that can be covered, Note 3 below.
Flexible cables wound on winding drums: The rated currents of cables used on winding drums should be reduced by the following factors: a) Radial drum b) Vented cylindrical drum: Vented: 85% 1 cable layer: 85% Non-vented: 75% 2 cable layers: 65% 3 cable layers: 45% 4 cable layers: 35% A radial drum is one in which spiral layers of cable are accommodated between spaced flanges; if
If equipped with solid flanges, the rated currents given above must be reduced and the drum is described as non-vented. If the flanges have adequate openings, the drum is described as vented.

A ventilated cylindrical cable drum is one in which cable layers are accommodated between widely spaced flanges, and the drum and end flanges have adequate ventilation openings.

When the cable may be covered or wound during loading, or when air movement over the cable is restricted, the rated current must be reduced. It is not possible to specify the reduction amount, but the rating factor table for winding drums can be used as a guide.
For 180°C cables, ambient temperature ratings allow for a conductor operating temperature of up to 150°C. Consult the cable manufacturer for more information.
When the cables in this table are to be connected to equipment or accessories designed to operate at a temperature lower than the maximum operating temperature of the cable, the cables must be rated for the maximum operating temperature of the equipment or accessory (see Regulation 512.1.5).

When grouping a cable in this table with other cables, the cable must be rated for the lowest maximum operating temperature of any of the cables in the group (see Regulation 512.1.5).

Table 4F2B – IEE

LINK TO THE TABLE: Table 4F2B – IEE

Table 4F3A Unarmored Flexible Cables – IEE

LINK TO TABLE: Table 4F3A Unarmored Flexible Cables – IEEE

Table 4F3B – IEE

Voltage drop (in ampere-meters):

Conductor operating temperature: 60°C*

Cross-sectional area of ​​the conductorDC or AC single-phase.Three-phase alternating current.
123
(mm2)(mV/A/m)(mV/A/m)
0.59380
0.756254
14640
1.2537
1.53227
2.51916
41210

Note:

* The values ​​tabulated above are for flexible cables insulated with thermoplastic or thermosetting material at 60 °C and, for other types of flexible cables, they must be multiplied by the following factors:

For cables insulated with thermoplastic or thermosetting material at 90 °C: 1,09

150°C: 1,31

185 °C: fiberglass: 1,43

Current and voltage drop ratings II – IEE

Related Articles

STANDARD

British cable standards BS4737-3.30:1986 Intrusion alarm systems. Specification for PVC insulated cables for interconnect wiring.