Minimum permissible bending radius according to DIN VDE 0298 part 3. Rated voltage up to 0,6 / 1 kV.

Cable outer diameter / Flat cable thickness in mm

Cables for fixed installation
to
10 mm
above/up to
10-25 mm
to over
25 mm
for fixed installation4xd4xd4xd
for internal wiring1xd2xd3xd
Flexible cables
Cable outer diameter / Flat cable thickness in mm
even about/even about/even about
8mm 8-12mm 12-20mm 20mm
for fixed installation3xd3xd4xd4xd
in free movement3xd4xd5xd5xd
in the introduction3xd4xd5xd5xd
Flexible cables
with restricted orientation
Cable outer diameter / Flat cable thickness in mm
even about/even about/even about
8mm 8-12mm 12-20mm 20mm
Drum operation5xd5xd5xd6xd
Cable trolley operation3xd4xd5xd5xd
Drag chain operation4xd4xd5xd5xd
Roller deviation8xd8xd8xd8xd

Minimum permissible bending radius: according to DIN VDE 0298 part 3