A servomotor can exhibit excellent repeatability and dynamics, but suffer performance losses due to an inadequate cable specification. Sizing cables for servomotors requires analyzing more than just the nominal conductor cross-section: the combination of motor, servo drive, travel, mechanical movement, and environment defines the correct solution. In critical applications, an undersized cable can increase temperature, boost losses, trigger drive alarms, and reduce system lifespan.
In high-cycle machines, robotic cells, positioning axes, bridges, cutting systems, and automated lines, cable selection must simultaneously consider current carrying capacity, voltage drop, electromagnetic compatibility, and mechanical strength. Engineering must treat the cable as an active part of the automation architecture, not as a generic interconnection item.
What determines the cable sizing for servomotors?
The starting point is to gather the electrical data for the motor and servo drive. Nominal current, RMS current during the cycle, peak current, supply voltage, drive switching frequency, and total circuit length are information that cannot be estimated solely from the power in kW. Two servo motors with the same power may require different cables when operating with different acceleration cycles, very different cable lengths, or opposite thermal conditions.
The motor's rated current determines its continuous driving capacity. However, in shafts with frequent accelerations and decelerations, the RMS current of the cycle may be more representative of the thermal load on the conductors. The peak current, in turn, needs to be checked to ensure that transients do not produce voltage drops incompatible with the drive's operation. It is incorrect to choose the cross-section solely based on the maximum instantaneous current, as this can lead to oversizing the design without addressing factors such as installation, shielding, or bending.
The permissible current of a cable depends on its construction and the actual application conditions. Ambient temperature, number of grouped circuits, ventilation, installation in cable trays, conduits, or raceways, as well as the maximum temperature of the conductor and insulation, directly alter the ampacity. Generic tables are initial references, but validation should consider the manufacturer's data and the correction factors applicable to the project.
Voltage drop and circuit length
The greater the distance between the servo drive and the motor, the greater the electrical resistance of the circuit and, consequently, the voltage drop. In three-phase systems, an initial assessment can use the following relationship:
`ΔV = √3 × I × L × (R × cos φ + X × sin φ)`
In this expression, I is the design current, L is the length in one direction, R is the conductor resistance per unit length, and X is the reactance. The calculation serves as a basis, but does not eliminate the need to evaluate the characteristics of the PWM drive. In long cables, the interaction between the inverter or servo drive output, the cable capacitance, and the motor impedance can be more critical than the steady-state voltage drop.
There is an engineering decision involved: increasing the cross-section reduces losses and voltage drop, but increases cost, minimum bending radius, mass per meter, and stress on the cable carrier. Therefore, the best cross-section is not automatically the largest available. It is the one that meets the electrical performance and mechanical condition of the equipment with a coherent technical margin.
Cables for servo drives are not conventional power cables.
The output of a servo drive consists of high-frequency pulses with fast edges. This behavior can generate overvoltages due to reflected wave effects, common-mode currents, electromagnetic interference, and increased stress on the insulation system. A standard power cable, even with sufficient cross-section for the current, may not offer the necessary construction for this application.
Cables for servomotors typically require insulation compatible with the voltage stresses of PWM, proper conductor geometry, and efficient shielding . Shielding should reduce electromagnetic emissions and improve system immunity, especially when the motor cable runs near encoder cables, instrumentation, industrial networks, or low-power analog signals.
The continuity of the shielding is as important as its presence. Inadequate connections, long pigtails, or incomplete grounding compromise effectiveness at high frequencies. In most applications, terminating the shielding with 360-degree contact at connectors, cable glands, or appropriate metal elements is superior to improvised solutions. The final method should follow the grounding design, the drive manufacturer's recommendation, and the machine's electromagnetic compatibility requirements.
It is also necessary to separate the power function from the feedback function. The encoder works with sensitive signals and requires suitable pairs, shielding, and electrical characteristics compatible with the protocol used. There are hybrid constructions that combine power and signal in a single cable, useful when space is limited or when the motor architecture was designed for this arrangement. Even so, the choice depends on the compatibility between the motor, drive, connectors, and installation path.
Flexion, torsion, and environment change the specification.
In a fixed panel, the cable operates predominantly under static conditions. In a robot, gantry, or linear axis, it can undergo millions of cycles of bending, acceleration, repetitive curvature, and in some cases, torsion. Applying a static cable to a cable carrier is a recurring source of premature failure, even when the electrical section is correct.
For continuous movement, the minimum operating bending radius, speed, acceleration, travel, conveyor type, and load rate must be verified. The conductor construction, stranding, insulation materials, outer covering, and internal arrangement of elements determine resistance to mechanical fatigue. Cables for robotics may require additional torsional performance, while suspended or lifting applications demand attention to tensile strength and self-weight.
The environment completes the analysis. Oils, greases, cutting fluids, salt spray, UV radiation, abrasion, washing, high or low temperatures, and flame hazard may require specific compounds and regulatory requirements. The outer sheath should be selected based on actual exposure, not the cable's appearance. An inadequate sheath may harden, crack, or lose chemical resistance before the conductor exhibits any electrical problems.
Engineering method for specifying the solution
The specification begins with a complete circuit survey: motor model, drive, voltage, DC and peak current, length, connectors, installation type, and motion profile. Next, the current capacity is calculated with correction factors, the voltage drop is checked, and the length limits specified by the drive manufacturer are evaluated.
Next comes the signal integrity and EMC analysis. The need for shielding, grounding topology, segregation from other circuits, and compatibility between cable, filters, and reactors (when applicable) must be confirmed. For long runs, sinusoidal filters, dv/dt filters, or reactors may be necessary to limit stress on the motor insulation. These features do not replace the correct cable selection but are integral to the system solution.
Finally, engineering validates the mechanical and environmental conditions. The cable must withstand the expected bending radius, the anticipated number of cycles, the presence of chemical agents, and the installation's safety requirements. Technical documentation, material traceability, and quality control help maintain repeatability between replacements and future machine expansions.
Standards such as IEC 60204-1 and IEC 61800-3 can guide aspects of electrical machine installation and electromagnetic compatibility, but the application of each requirement depends on the project scope, the market served, and contractual requirements. In projects with specific standards, compliance must be defined from the specification stage, and not only during commissioning.
Innovcable develops special cables for industrial applications that demand electrical performance, mechanical strength, and reliability in the field. When application data is addressed from the outset, the cable ceases to be a risk variable and becomes a key component supporting the availability your process needs to deliver.
How to size cables for industrial servomotors.
Related Articles

Everything about concentric cable: standards and applications.
Concentric Cable: A Complete Technical Guide for Engineers and Installers. Concentric cable represents an advanced engineering solution for networks.

Trends in Industrial Cables for 2026
Trends in industrial cabling combine automation, data, safety, and durability. Learn how to specify solutions for critical field environments.

Cable selection for frequency inverter
Selecting the right cable for your inverter reduces faults, noise, and downtime. Learn about the electrical, construction, and regulatory criteria for a safe specification.

Critical Safety: When to Specify a High-Performance vs. Conventional Fire Cable
In life safety systems, such as fire detection and alarm systems, the cable specification
Knowledge Academy: Technical information, standards and applications

Tables and Codes for Thermocouples
International Color Code for Compensation and Extension Cables and Wires - Cable Code - Error Limit Table

NBR 5410 Sizing Tables
DOWNLOAD NBR 5410 DIMENSIONING TABLES Explanation With the aim of offering a practical tool to assist in the work of

Color code tables
Color code according to DIN 47100 No. Colour Short Form 1 WHITE WH 2 BROWN BN 3

TABLE AND GUIDELINES AWG X METRIC CONVERSION (mm²)
Unveiling the AWG Standard: A Technical Guide for Professionals and Enthusiasts – American Wire Gauge (AWG) to Metric (mm²) Conversion
Questions? Send a message to the expert.
Access to cutting-edge scientific information is the fuel for innovation. These are the databases, journals, and repositories that our R&D team uses to stay at the forefront of global technical and scientific knowledge.
Databases, Repositories and Search Engines:
- IEEE Xplore Digital Library: The most crucial digital library for electrical and computer engineering. IEEE
- ACM Digital Library: A reference for the field of computer science and information technology. ACM
- Science Direct: Extensive collection of scientific publications and books from the publisher Elsevier. SCIENCE DIRECT
- Scopus: The largest database of abstracts and citations from peer-reviewed literature. scopus
- CAPES Journal Portal: It provides access to international scientific output for the teaching and research community in Brazil. CAPES
- Google Scholar Search tool focused on academic literature. GOOGLE SCHOLAR
- Brazilian Digital Library of Theses and Dissertations (BDTD): Repository of scientific output from Brazilian teaching and research institutions. BDTD
- Directory of Open Access Journals (DOAJ): A directory of high-quality open access journals. DOAJ
Prominent Scientific Periodicals and Journals:
- Naval, Offshore and Petroleum Engineering:
- Ocean Engineering (Elsevier)
- Journal of Ship Research (SNAME)
- Journal of Petroleum Science and Engineering (Elsevier)
- Journal of Marine Science and Engineering (MDPI)
- Journal of the Brazilian Society of Naval Engineering (SOBENA)
- Electrical, Electronic and Telecommunications Engineering:
Products

Profibus DP DeepSea® Armed SHF2
Busbar cable; PROFIBUS DP; Fixed installation; Nominal characteristic impedance: 150 Ω; 1x2x0,64; SHF2; Flame retardant: IEC 60332-1-2; violet; 8 mm

MariTimus® Single-Core Marine Power and Control Cable 0,6/1 kV XLPE/SHF1 (LSOH) Armored and Flame Retardant
Maritimus® Single-Core Naval Power and Control Cable; Armored; Max. 300,00 mm²; 0,6/1 kV; 1 conductor; XLPE / SHF1; Flame Retardant; +90°C; IEC 60092

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Fire Resistant IEC 60331
Maritimus® Single-Core Marine Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Armored and Fire Resistant IEC 60331
Maritimus® Armored Multicore Naval Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331