An intermittent shutdown in an automated cell rarely originates in the PLC. Often, it stems from a cable specification based solely on voltage and number of conductors, without considering movement, electromagnetic interference, environment, and expected lifespan. Knowing how to specify cables for automation transforms a seemingly simple item into an active part of process reliability.
In machines, production lines, motion systems, and process plants, cables carry power, control signals, data, and feedback. Each of these functions requires specific design characteristics. Using an unsuitable cable can lead to noise in analog signals, communication failures, overheating, sheath cracks, conductor breakage, and unscheduled downtime.
How to specify cables for automation without losing critical requirements.
The specification should begin with the application, not the catalog. Before defining nominal cross-section, shielding, or sheathing material, it is necessary to understand what equipment will be connected, how the cable will be installed, and what real-world conditions it will face during operation.
The first step is to separate the circuits by function. Control cables for contactors and discrete sensors have different needs than cables for instrumentation, industrial communication, servomotors, or frequency inverters. Grouping everything under the generic name of "automation cable" creates room for incompatibilities that only appear after commissioning.
A consistent technical request should include, at a minimum, the following information:
- Circuit function, rated voltage, current, and type of signal transmitted;
- number of lanes, driver cross-section, and need for pairs or trios;
- Installation method, path length, and minimum available bending radius;
- Motion condition, such as fixed installation, occasional bending, cable carrier or twisting;
- Operating environment, including oil, moisture, chemical agents, UV, abrasion, heat, and fire hazard;
- Project guidelines, end-customer requirements, and required documentation.
This information allows engineers to evaluate the most suitable construction. In critical applications, the initial cost of the cable represents a small fraction compared to the impact of a shutdown, field replacement, or loss of signal traceability.
Electrical sizing: more than just voltage and cross-section.
The rated voltage must be compatible with the circuit and the installation class, but this alone does not resolve the specification. The conductor cross-section must meet the load current, the permissible voltage drop, the short-circuit capacity, and the thermal conditions of the cable bundle. A correctly sized conductor on a test bench may operate above the expected temperature when installed in a congested cable tray or in a hot environment.
In control circuits, the most common mistake is excessively reducing the cross-section to save material. Coils, solenoids, and actuators can experience voltage drop that compromises actuation, especially over long paths. In low-intensity signals, the central point may be the stability of the measurement, not the current carrying capacity.
For instrumentation, assess the need for twisted pairs or triples, as well as the capacitance and electrical resistance of the assembly. Analog signals, thermocouples, transmitters, and control loops respond differently to electrical disturbances. The cable construction must preserve signal integrity from the field to the panel or supervisory system.
Shielding and electromagnetic compatibility
The presence of frequency inverters, servo drives, switched-mode power supplies, and electronic drives has increased the importance of electromagnetic compatibility in industrial installations. In these environments, shielding defined merely as "optional" is often a risky decision.
The choice between collective shielding, individual shielding per pair, or a combination of both depends on the signal sensitivity and the level of surrounding interference. Collective shielding can serve a set of control circuits. For instrumentation with multiple pairs and independent signals, individual shielding reduces interference between the circuits themselves, while general shielding reinforces external protection.
It is also necessary to consider the material and covering of the shielding. Copper braid offers good protection and electrical continuity, while metallic tape may meet certain construction and requirements. The decision should be linked to the grounding design. Shielding without proper termination loses much of its function and may even create unwanted paths for stray currents.
In cables for inverters and servomotors, even greater care must be taken. The cable needs to withstand the electrical stresses associated with high-frequency pulses, help control electromagnetic emissions, and maintain the integrity of the connection between the drive and the motor. Using a conventional power cable in this section can result in insulation failures, noise in nearby equipment, and low system reliability.
Movement, bending, and twisting define mechanical engineering.
A cable installed on a stationary machine should not be automatically applied to a cable carrier . Continuous bending subjects conductors, insulation, shielding, and sheathing to repetitive stresses. For this condition, the construction needs to consider appropriate stranding, flexible materials, stable internal geometry, and abrasion-resistant sheathing.
The bending radius is another crucial factor. When the design requires tight bends, the cable needs to be developed for that condition. Forcing a radius smaller than recommended accelerates mechanical fatigue, even when the current and voltage are within limits.
In robotic applications, in addition to bending, continuous torsion may occur . In this case, the internal distribution of the elements and the behavior of the assembly during rotation are crucial. An unsuitable cable may exhibit displacement of internal components, shielding detachment, and premature breakage. The service life should be evaluated in operating cycles compatible with the machine's demands, not just by the product's external appearance.
Coverage and insulation for the real environment.
PVC, rubber compounds, polyurethane, and specialty materials offer different performance levels when exposed to oil, grease, cutting fluid, abrasion, weathering, ozone, flame, and temperature. There is no universally superior covering. The appropriate covering exists for each specific working condition.
In outdoor areas, for example, resistance to UV radiation and moisture must be considered. In environments with oil and chemical agents, the compatibility of the compound must be proven for the fluids involved. In steelmaking, mining, ports, and areas of heavy handling, abrasion and impact may require solutions with greater mechanical protection.
When fire safety requirements are in place, clearly specify the expected behavior: no flame propagation, low smoke emission, absence of halogens, circuit maintenance in case of fire, or a combination of these criteria. These are different attributes, applicable according to the risk analysis and the standards of the project.
Standards, traceability and performance validation
National and international standards do not replace application analysis, but they establish objective criteria for construction, testing, and performance. Projects may require compliance with ABNT, IEC, American standards, naval requirements, or references such as NEK-606, depending on the segment and the client.
During the purchasing phase, the description must indicate the applicable standard, voltage, conductor composition, insulation, sheath, shielding, flexibility class, colors or identification, length, and testing requirements. The more critical the process, the higher the level of documentation and traceability per batch must be.
It's also worth validating the solution before large-scale installation. On a new machine or a recurring replacement, a controlled field test allows observation of bending radius, conveyor belt accommodation, shielding behavior, and steady-state performance. This precaution reduces the chance of turning the start-up into an unintentional materials test.
In this respect, Innovcable acts as an engineering partner, developing special cables on demand for specific electrical, mechanical, and environmental conditions. When the project requires proven performance, in-house manufacturing, and quality control, the specification must reflect the reality of the application from the outset.
The best cable for automation isn't the one with the most features, but the one that delivers performance compatible with the circuit, environment, and operating cycle. Incorporate field data into the specification, involve engineering before purchasing, and treat every meter of cable as part of your process availability.
How to specify cables for industrial automation
Related Articles

Everything about concentric cable: standards and applications.
Concentric Cable: A Complete Technical Guide for Engineers and Installers. Concentric cable represents an advanced engineering solution for networks.

Trends in Industrial Cables for 2026
Trends in industrial cabling combine automation, data, safety, and durability. Learn how to specify solutions for critical field environments.

Cable selection for frequency inverter
Selecting the right cable for your inverter reduces faults, noise, and downtime. Learn about the electrical, construction, and regulatory criteria for a safe specification.

Critical Safety: When to Specify a High-Performance vs. Conventional Fire Cable
In life safety systems, such as fire detection and alarm systems, the cable specification
Knowledge Academy: Technical information, standards and applications

Tables and Codes for Thermocouples
International Color Code for Compensation and Extension Cables and Wires - Cable Code - Error Limit Table

NBR 5410 Sizing Tables
DOWNLOAD NBR 5410 DIMENSIONING TABLES Explanation With the aim of offering a practical tool to assist in the work of

Color code tables
Color code according to DIN 47100 No. Colour Short Form 1 WHITE WH 2 BROWN BN 3

TABLE AND GUIDELINES AWG X METRIC CONVERSION (mm²)
Unveiling the AWG Standard: A Technical Guide for Professionals and Enthusiasts – American Wire Gauge (AWG) to Metric (mm²) Conversion
Questions? Send a message to the expert.
Access to cutting-edge scientific information is the fuel for innovation. These are the databases, journals, and repositories that our R&D team uses to stay at the forefront of global technical and scientific knowledge.
Databases, Repositories and Search Engines:
- IEEE Xplore Digital Library: The most crucial digital library for electrical and computer engineering. IEEE
- ACM Digital Library: A reference for the field of computer science and information technology. ACM
- Science Direct: Extensive collection of scientific publications and books from the publisher Elsevier. SCIENCE DIRECT
- Scopus: The largest database of abstracts and citations from peer-reviewed literature. scopus
- CAPES Journal Portal: It provides access to international scientific output for the teaching and research community in Brazil. CAPES
- Google Scholar Search tool focused on academic literature. GOOGLE SCHOLAR
- Brazilian Digital Library of Theses and Dissertations (BDTD): Repository of scientific output from Brazilian teaching and research institutions. BDTD
- Directory of Open Access Journals (DOAJ): A directory of high-quality open access journals. DOAJ
Prominent Scientific Periodicals and Journals:
- Naval, Offshore and Petroleum Engineering:
- Ocean Engineering (Elsevier)
- Journal of Ship Research (SNAME)
- Journal of Petroleum Science and Engineering (Elsevier)
- Journal of Marine Science and Engineering (MDPI)
- Journal of the Brazilian Society of Naval Engineering (SOBENA)
- Electrical, Electronic and Telecommunications Engineering:
Products

Profibus DP DeepSea® Armed SHF2
Busbar cable; PROFIBUS DP; Fixed installation; Nominal characteristic impedance: 150 Ω; 1x2x0,64; SHF2; Flame retardant: IEC 60332-1-2; violet; 8 mm

MariTimus® Single-Core Marine Power and Control Cable 0,6/1 kV XLPE/SHF1 (LSOH) Armored and Flame Retardant
Maritimus® Single-Core Naval Power and Control Cable; Armored; Max. 300,00 mm²; 0,6/1 kV; 1 conductor; XLPE / SHF1; Flame Retardant; +90°C; IEC 60092

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Fire Resistant IEC 60331
Maritimus® Single-Core Marine Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Armored and Fire Resistant IEC 60331
Maritimus® Armored Multicore Naval Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331