A production stoppage caused by a cable rarely begins at the moment of rupture. In most cases, the origin lies in an incompatible specification, a disregarded bend radius, a poorly executed termination, or a process condition that was not considered in the design. Understanding how to prevent cable failures requires treating the component as an active part of the system engineering, and not as a generic item to be purchased.
In critical industrial applications, cable is simultaneously subjected to electrical, mechanical, thermal, and chemical stresses. A solution that works well in a fixed installation can quickly fail in a cable carrier, on mobile equipment, in a marine environment, or near frequency inverters. Prevention begins before the quote: it begins with correctly defining the application.
How to prevent cable failures from the specification stage.
The selection process must consider more than just nominal voltage, conductor cross-section, and number of conductors. These data are fundamental, but they alone do not determine if the product will withstand the expected operational cycle. It is necessary to evaluate the environment, the type of movement, exposure to external agents, electromagnetic compatibility, and the regulatory requirements of the project.
In an instrumentation cable , for example, signal integrity can be as relevant as electrical conductivity. Shielding, pairs or triples, capacitance, and grounding need to be defined according to the control system. In circuits powered by frequency inverters, the insulation must withstand voltage peaks and the stresses associated with high frequency. In mobile automation applications, the conductor, insulation, stranding, shielding, and sheathing assembly must be designed for continuous bending.
A well-constructed technical specification answers, at a minimum, these questions:
- Will the cable be installed in a fixed position, will it bend occasionally, or will it move continuously?
- What is the available bending radius on the equipment and during installation?
- Are there any signs of oil, grease, abrasion, moisture, salinity, solar radiation, chemicals, or flame present?
- What are the actual minimum and maximum operating temperatures?
- Does the circuit require shielding, low smoke emission, fire resistance, or specific fire performance?
- What customer, facility, and industry standards need to be met?
When this information is unavailable, the tendency is to specify by price or by superficial equivalence. This approach transfers the risk to commissioning and maintenance. In installations with high shutdown costs, the choice should consider the total cost of operation, not just the initial cost per meter.
Electrical sizing cannot ignore the process.
Thermal undersizing is a recurring cause of premature degradation. The conductor cross-section must be defined by the current, the permissible voltage drop, the installation method, the ambient temperature, the grouping of circuits, and the thermal dissipation capacity. A correctly sized cable in a vented tray may operate outside of normal conditions when installed in conduit, buried, or grouped with other loaded circuits.
It is also necessary to analyze transient currents and special regimes. Motor starts, load cycles, harmonics, and inverter power supplies modify the electrical behavior of the system. In medium voltage systems, details such as metallic shielding, semiconductor, insulation geometry, and proper terminations directly influence the reliability of the assembly.
Excessive heating accelerates the aging of insulation. Over time, the material may lose flexibility, develop cracks, or reduce its dielectric strength. The final failure may occur at a seemingly isolated point, but the cause will be distributed throughout the history of thermal overload.
Installation: even the right cable can fail if it's incorrectly installed.
A technically sound product can be damaged even before it goes into operation. Excessive traction, use of incompatible lubricants, dragging over abrasive surfaces, and improper storage compromise the coating and internal structure. Therefore, installation must have a procedure, defined responsibilities, and inspection criteria.
The minimum bending radius deserves special attention. Tight bends can deform insulation, displace shields, alter pair geometry, and concentrate stress on the conductors. In data, instrumentation, and control cables, this can cause signal instability before generating an obvious electrical fault. In flexible power cables, the consequence can be the progressive rupture of the conductor's elementary wires.
In cable carrier systems , simply choosing a flexible cable is not enough. It's necessary to verify the travel, speed, acceleration, internal arrangement, cable diameter, usable height of the carrier, and the separation between circuits. Compressed, crossed, or incorrectly slack cables suffer wear due to friction and torsion. The assembly must allow for guided movement, without jamming and without concentrated forces at the carrier's exit.
Terminations are also critical points. Excessive stripping, over-torque tightening, improper terminal crimping, poor sealing, and incorrect shield grounding create points of high resistance, overheating, or susceptibility to interference. The quality of the connection must match the cable's performance.
Materials control and environmental compatibility
Harsh environments require materials compatible with the actual exposure. A PVC covering may be suitable for certain industrial installations, but not necessarily for conditions involving oil, intense abrasion, low temperatures, or permanent sun exposure. Rubber compounds, polyurethane, special polyolefins, and materials with specific flame-retardant or low-smoke emission characteristics may be necessary, depending on the risk and applicable standard.
In naval and offshore areas, humidity, salt spray, oil, and fire safety requirements all play a role. In mining, abrasion, impact, dust, and heavy handling change the selection criteria. In photovoltaic parks, UV radiation, thermal variation, and continuous outdoor exposure are key factors. There is no universal cable for these conditions.
Compatibility must include accessories. Cable glands, conduits, connectors, junction boxes, and fasteners must maintain their degree of protection and not cause crushing or cutting of the sheath. A suitable cable connected by an incompatible cable gland remains a vulnerability of the system.
Evidence-driven maintenance reduces unexpected failures.
Preventive maintenance should not be limited to occasional visual inspections. It needs to be defined according to the criticality of the circuit, the history of failures, the environment, and the type of stress. Mobile circuits and those exposed to heat, chemicals, or vibration require higher frequency maintenance than protected fixed installations.
Visual inspection is useful for identifying dryness, discoloration, cracks, abrasion, deformation, crush points, and moisture ingress. However, many defects develop internally. Insulation, continuity, contact resistance, thermography, and specific signal tests help detect anomalies before operational interruption.
Thermography, for example, can reveal overheating in connections, terminals, and points with poor contact. It does not replace sizing or physical inspection, but it offers an objective reading of the system's behavior under load. Similarly, a downward trend in insulation resistance warrants investigation even if the circuit is still operating.
Record the results by circuit and by equipment. Temperature data, bending cycles, maintenance occurrences, load, and environment transform reactive interventions into technical decisions. When a failure recurs, the focus should be on the root cause: it could be the assembly, the material selection, the equipment dynamics, or a change in the process that the original design did not foresee.
Custom engineering for non-standard applications
Industrial projects often combine requirements not found in conventional catalog products. These may include the need for specific shaping, differentiated shielding, a covering resistant to a particular fluid, a span length compatible with the installation, or simultaneous compliance with customer and industry standards.
In these situations, customization doesn't just mean changing colors or length. It means developing a construction capable of sustaining the required performance, with material criteria, testing, and quality control aligned with the application. Innovcable operates precisely at this interface between field requirements and the manufacture of special cables, supporting projects that do not allow for improvisation in the specification.
The best decision is to involve cable engineering during the design phase or when replacing a recurring item. Providing information such as installation photos, load data, movement types, drawings, fault history, and required standards reduces uncertainty and speeds up solution selection.
In operations that depend on continuity, the cable must be treated as a reliability asset. Accurate specification, methodical installation, and field performance monitoring create a technical barrier against failures that cost production, safety, and time.
How to prevent failures in industrial cables
Related Articles

Everything about concentric cable: standards and applications.
Concentric Cable: A Complete Technical Guide for Engineers and Installers. Concentric cable represents an advanced engineering solution for networks.

Trends in Industrial Cables for 2026
Trends in industrial cabling combine automation, data, safety, and durability. Learn how to specify solutions for critical field environments.

Cable selection for frequency inverter
Selecting the right cable for your inverter reduces faults, noise, and downtime. Learn about the electrical, construction, and regulatory criteria for a safe specification.

Critical Safety: When to Specify a High-Performance vs. Conventional Fire Cable
In life safety systems, such as fire detection and alarm systems, the cable specification
Knowledge Academy: Technical information, standards and applications

Tables and Codes for Thermocouples
International Color Code for Compensation and Extension Cables and Wires - Cable Code - Error Limit Table

NBR 5410 Sizing Tables
DOWNLOAD NBR 5410 DIMENSIONING TABLES Explanation With the aim of offering a practical tool to assist in the work of

Color code tables
Color code according to DIN 47100 No. Colour Short Form 1 WHITE WH 2 BROWN BN 3

TABLE AND GUIDELINES AWG X METRIC CONVERSION (mm²)
Unveiling the AWG Standard: A Technical Guide for Professionals and Enthusiasts – American Wire Gauge (AWG) to Metric (mm²) Conversion
Questions? Send a message to the expert.
Access to cutting-edge scientific information is the fuel for innovation. These are the databases, journals, and repositories that our R&D team uses to stay at the forefront of global technical and scientific knowledge.
Databases, Repositories and Search Engines:
- IEEE Xplore Digital Library: The most crucial digital library for electrical and computer engineering. IEEE
- ACM Digital Library: A reference for the field of computer science and information technology. ACM
- Science Direct: Extensive collection of scientific publications and books from the publisher Elsevier. SCIENCE DIRECT
- Scopus: The largest database of abstracts and citations from peer-reviewed literature. scopus
- CAPES Journal Portal: It provides access to international scientific output for the teaching and research community in Brazil. CAPES
- Google Scholar Search tool focused on academic literature. GOOGLE SCHOLAR
- Brazilian Digital Library of Theses and Dissertations (BDTD): Repository of scientific output from Brazilian teaching and research institutions. BDTD
- Directory of Open Access Journals (DOAJ): A directory of high-quality open access journals. DOAJ
Prominent Scientific Periodicals and Journals:
- Naval, Offshore and Petroleum Engineering:
- Ocean Engineering (Elsevier)
- Journal of Ship Research (SNAME)
- Journal of Petroleum Science and Engineering (Elsevier)
- Journal of Marine Science and Engineering (MDPI)
- Journal of the Brazilian Society of Naval Engineering (SOBENA)
- Electrical, Electronic and Telecommunications Engineering:
Products

Profibus DP DeepSea® Armed SHF2
Busbar cable; PROFIBUS DP; Fixed installation; Nominal characteristic impedance: 150 Ω; 1x2x0,64; SHF2; Flame retardant: IEC 60332-1-2; violet; 8 mm

MariTimus® Single-Core Marine Power and Control Cable 0,6/1 kV XLPE/SHF1 (LSOH) Armored and Flame Retardant
Maritimus® Single-Core Naval Power and Control Cable; Armored; Max. 300,00 mm²; 0,6/1 kV; 1 conductor; XLPE / SHF1; Flame Retardant; +90°C; IEC 60092

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Fire Resistant IEC 60331
Maritimus® Single-Core Marine Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Armored and Fire Resistant IEC 60331
Maritimus® Armored Multicore Naval Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331