An intermittent PLC shutdown, an unstable instrument reading, or a communication failure in an industrial network rarely originates in the software. In many cases, the source lies in the physical signal path. Knowing how to protect cables against interference is an engineering decision that reduces unproductive diagnostics, process losses, and safety risks.
In industrial environments, power cables, frequency inverters, motor starters, contactors, welding, lighting, and radio systems can generate electromagnetic interference. When the specification and installation do not consider this scenario, the cable ceases to simply transmit power or data and begins to pick up noise. The result can range from small oscillations to improper commands, packet loss, and operational unavailability.
Interference does not have a single origin.
Electromagnetic interference, also called EMI, can reach a circuit through conduction, capacitive coupling, inductive coupling, or radiation. Each mechanism requires its own control measures. Treating all cases simply with thicker shielding is a common mistake and, in critical designs, can create a false sense of security.
Conducted interference travels through shared conductors, power supplies, or grounding references. Capacitive coupling occurs due to the proximity of circuits with different electrical potentials, especially in long, parallel cables. Inductive coupling is more associated with magnetic fields generated by high currents, such as those present in motor power supplies. Radiated interference, in turn, propagates through the environment and can affect more sensitive circuits.
The analysis must consider frequency, power of the emitting source, distance, length of the parallel path, signal type, and system impedance. An instrumentation cable carrying a low-voltage analog signal requires different considerations than an industrial Ethernet cable or a 24 VDC control circuit.
How to protect cables against interference in the specification
Protection begins before purchase. The cable needs to be specified according to its actual application, and not just by the number of conductors, nominal cross-section, and insulation voltage. In areas of automation, instrumentation, process control, and drives, the electrical and mechanical construction of the cable directly influences its noise immunity.
For analog signals , twisted pairs help reduce induction pickup, as the incident fields tend to act more evenly on both conductors. In differential signals, this characteristic favors common-mode rejection by the receiving equipment. When there are multiple pairs in the same cable, individual shielding per pair may be necessary to limit crosstalk between circuits and protect independent measurement channels.
Collective shielding is recommended when an additional barrier is desired for the set of pairs or veins. It can be formed by metallic tape, copper braid, or a combination of both. The choice depends on the frequency range, the required flexibility, the shielding coverage, and the mechanical conditions of installation. Tapes offer good coverage, while braids typically offer lower impedance under certain conditions and greater mechanical resistance.
In frequency inverter and servomotor applications , the cable must be designed to withstand the effects of high voltage variation rates, common-mode currents, and electromagnetic emissions associated with switching. Standard power cables may underperform in this scenario. Shielding, protective conductor arrangement, and drive compatibility are system components, not accessory details.
Shielding only works with the correct termination.
A disconnected, interrupted, or improperly grounded shield can lose much of its efficiency. At high frequencies, the termination point becomes as relevant as the shield material. Ideally, 360-degree peripheral contact should be achieved between the shield and the connector, cable gland, or suitable fastening element.
Long pigtails – those wire extensions made from the mesh to reach the ground terminal – increase inductance and impair high-frequency efficiency. They may be acceptable under specific, low-frequency conditions, but should not be treated as a standard solution for systems subject to noise from inverters, industrial communications, or fast drives.
There is also no universal rule for grounding at one or both ends. For low frequencies and certain instrumentation topologies, grounding the shield at only one point can help prevent loop currents. In installations with high-frequency interference, connecting at both ends usually offers better electromagnetic performance. The definition should follow the electrical design, the grounding architecture, the equipment manufacturer's recommendations, and applicable regulatory requirements.
Physical separation is a high-impact measure.
Even a well-constructed cable can suffer interference when improperly installed. Segregation between power, control, instrumentation, and data circuits needs to be planned in cable trays, conduits, raceways, panels, and crossings.
Avoid prolonged parallel runs between signal cables and motor feeders. When crossing is unavoidable, doing so at close to 90 degrees reduces the coupling area. In extensive installations, the minimum distance between circuits should be defined by the energy level involved, the type of cable, the presence of grounded metal partitions, and the process requirements.
Within switchboards, proper routing is crucial. Analog input cables, industrial networks, and encoder signals should not share the same output path as inverters or contactors. Physically separating circuits, maintaining continuity of metal surfaces, and using well-grounded mounting plates contribute to a more predictable installation.
Grounding needs to be treated as a system.
The grounding grid serves not only to protect against electric shock. It also defines return paths for high-frequency currents and directly influences the behavior of shields, housings, panels, and equipment. Loose connections, painted or oxidized surfaces, or surfaces with low contact area increase impedance and compromise noise control.
In automated machines and lines, equipotential bonding is a key word. Metal structures, panel doors, cable trays, and housings must maintain reliable electrical continuity. A panel door connected only by hinges, for example, may not offer an adequate path for high frequencies. Appropriate metal straps and low-impedance connections can make a difference in the overall performance.
It's important to remember that inadequate grounding cannot be corrected simply by adding rods to the ground. The internal electromagnetic behavior of the installation, including equipotential bonding and return path, needs to be evaluated by qualified professionals.
Choose the cable according to the environment and movement.
Protection against interference cannot sacrifice mechanical durability. In cable carriers , robotics, mobile equipment, mining, marine applications, or outdoor areas, the cable still needs to withstand bending, abrasion, oil, moisture, solar radiation, vibration, and tensile stress.
Inadequate shielding for continuous motion can rupture, lose coverage, or reduce its lifespan sooner than expected. Similarly, a construction that is too rigid can hinder installation or accelerate fatigue in dynamic applications. Engineering must balance EMC performance, bending radius, bending cycles, chemical resistance, and temperature requirements.
High-risk projects deserve documentary and technical validation. Applicable standards, construction characteristics, flexibility class, insulation material, shielding, operating voltage, and environmental conditions must be included in the specification. When the application deviates from the standard, cable customization can eliminate improvised adaptations in the field.
Interference diagnosis: start with the route
When a fault is already present, replacing equipment without investigating the cabling usually increases costs and downtime. The assessment should begin with mapping the affected circuits, nearby power sources, and the cable routing. It is helpful to check if the problem arises after an inverter is switched on, a motor starts, a load is switched, or a change in panel routing occurs.
Inspect shield terminations, electrical continuity, connector crimping, braid integrity, separation between routes, and grounding points. Then, compare the installed cable construction with that required by the application. A process instrument with a low-intensity signal connected by unshielded, twisted-pair cable will hardly exhibit stable behavior on a power-shared route.
Innovcable develops special cables for scenarios where electrical performance, operational resistance, and project suitability need to go hand in hand. In critical applications, the right decision is to treat the cable as an active part of the system engineering.
The best protection doesn't come from a single component. It results from a combination of technically suitable cable, well-terminated shielding, controlled grounding, and disciplined installation. When these factors are defined during the design phase, the operation gains more than just noise immunity: it gains predictability for production, measurement, and control without avoidable interruptions.
How to protect cables against interference
Related Articles

Everything about concentric cable: standards and applications.
Concentric Cable: A Complete Technical Guide for Engineers and Installers. Concentric cable represents an advanced engineering solution for networks.

Trends in Industrial Cables for 2026
Trends in industrial cabling combine automation, data, safety, and durability. Learn how to specify solutions for critical field environments.

Cable selection for frequency inverter
Selecting the right cable for your inverter reduces faults, noise, and downtime. Learn about the electrical, construction, and regulatory criteria for a safe specification.

Critical Safety: When to Specify a High-Performance vs. Conventional Fire Cable
In life safety systems, such as fire detection and alarm systems, the cable specification
Knowledge Academy: Technical information, standards and applications

Tables and Codes for Thermocouples
International Color Code for Compensation and Extension Cables and Wires - Cable Code - Error Limit Table

NBR 5410 Sizing Tables
DOWNLOAD NBR 5410 DIMENSIONING TABLES Explanation With the aim of offering a practical tool to assist in the work of

Color code tables
Color code according to DIN 47100 No. Colour Short Form 1 WHITE WH 2 BROWN BN 3

TABLE AND GUIDELINES AWG X METRIC CONVERSION (mm²)
Unveiling the AWG Standard: A Technical Guide for Professionals and Enthusiasts – American Wire Gauge (AWG) to Metric (mm²) Conversion
Questions? Send a message to the expert.
Access to cutting-edge scientific information is the fuel for innovation. These are the databases, journals, and repositories that our R&D team uses to stay at the forefront of global technical and scientific knowledge.
Databases, Repositories and Search Engines:
- IEEE Xplore Digital Library: The most crucial digital library for electrical and computer engineering. IEEE
- ACM Digital Library: A reference for the field of computer science and information technology. ACM
- Science Direct: Extensive collection of scientific publications and books from the publisher Elsevier. SCIENCE DIRECT
- Scopus: The largest database of abstracts and citations from peer-reviewed literature. scopus
- CAPES Journal Portal: It provides access to international scientific output for the teaching and research community in Brazil. CAPES
- Google Scholar Search tool focused on academic literature. GOOGLE SCHOLAR
- Brazilian Digital Library of Theses and Dissertations (BDTD): Repository of scientific output from Brazilian teaching and research institutions. BDTD
- Directory of Open Access Journals (DOAJ): A directory of high-quality open access journals. DOAJ
Prominent Scientific Periodicals and Journals:
- Naval, Offshore and Petroleum Engineering:
- Ocean Engineering (Elsevier)
- Journal of Ship Research (SNAME)
- Journal of Petroleum Science and Engineering (Elsevier)
- Journal of Marine Science and Engineering (MDPI)
- Journal of the Brazilian Society of Naval Engineering (SOBENA)
- Electrical, Electronic and Telecommunications Engineering:
Products

Profibus DP DeepSea® Armed SHF2
Busbar cable; PROFIBUS DP; Fixed installation; Nominal characteristic impedance: 150 Ω; 1x2x0,64; SHF2; Flame retardant: IEC 60332-1-2; violet; 8 mm

MariTimus® Single-Core Marine Power and Control Cable 0,6/1 kV XLPE/SHF1 (LSOH) Armored and Flame Retardant
Maritimus® Single-Core Naval Power and Control Cable; Armored; Max. 300,00 mm²; 0,6/1 kV; 1 conductor; XLPE / SHF1; Flame Retardant; +90°C; IEC 60092

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Fire Resistant IEC 60331
Maritimus® Single-Core Marine Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Armored and Fire Resistant IEC 60331
Maritimus® Armored Multicore Naval Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331