TECHNICAL ARTICLES

A fault in shielded cables rarely begins as a complete shutdown. Generally, it first appears as intermittent noise in analog signals, loss of communication, unstable instrument readings, alarms without apparent cause, or improper equipment operation. In industrial plants, these symptoms can be confused with defects in sensors, inverters, PLCs, or grounding. However, the cable itself may be the source of the problem – especially when the shielding was poorly specified, damaged during installation, or improperly terminated.
Shielding is not a construction detail. It is an integral part of the system's electromagnetic compatibility strategy and, depending on the application, helps control external interference, reduce electromagnetic emissions, and preserve transmission integrity. Identifying the root cause of a failure requires evaluating the entire system: environment, signal type, grounding method, installation, handling, and the electrical and mechanical characteristics of the cable.
What characterizes a fault in shielded cables?
A shielded cable can have electrically sound conductors and still compromise its operation. This occurs when the shielding loses continuity, suffers partial breakage, has insufficient coverage for the level of interference, or fails to perform its function due to incorrect termination.
In instrumentation circuits, for example, shielding degradation can introduce noise into low-voltage, low-current signals. In industrial networks, the effect can be increased communication errors, packet loss, or device instability. In cables for servomotors and frequency inverters, an inadequate shielding solution can increase the effects of high-frequency interference on nearby systems.
The failure can also have a mechanical origin. Repeated bending, excessive traction, crushing, vibration, bending below the recommended radius, and movement on conveyor belts can break braided wires or degrade the metallic tape. Even without completely breaking the circuit, this damage reduces the efficiency of the electromagnetic protection and tends to worsen with operation.
Main causes of failure in shielded cables.
Specification incompatible with the application.
Choosing a shielded cable simply because it has a metallic braid does not guarantee performance in the field. The type of shielding, its covering, the presence of tape, the drain wire, the pair construction, and compatibility with frequency and environment must all match the application.
Instrumentation cables in areas with a high concentration of motors, contactors, and inverters require a different analysis than that applied to data cables in a panel. Similarly, a cable subjected to oil, abrasion, moisture, chemical agents, heat, or continuous movement needs to combine electromagnetic protection with insulation and sheathing materials appropriate to the environment.
In critical applications, the specification must consider the rated voltage, signal type, impedance (when applicable), current, temperature, bending class, flame requirements, and project standards. Shielding is part of this engineering, not an isolated feature.
Inadequate termination and grounding
Effective shielding can lose its performance in the final stage of installation. Long pigtails, connections with low contact area, improvised splices, and shielding left without continuity are recurring sources of interference.
For high frequencies, termination with a 360-degree peripheral contact tends to offer better performance than connection via a long drain wire. However, there is no single rule for all circuits. Grounding at one or both ends depends on the type of signal, the frequency involved, the equipotential bonding architecture, the risk of circulating currents, and the system's EMC criteria.
Instead of replicating generic practices, the engineering team should define the termination method based on the electrical design. In cables associated with frequency inverters, for example, controlling high-frequency interference requires specific care both in the cable and in the field connections and panel.
Damage during launch and installation
Many problems begin before commissioning. Dragging over abrasive surfaces, using unsuitable rollers, tensile strength exceeding design limits, and excessive clamping of cable glands can deform or break internal components.
Another critical point is the minimum bending radius. When the cable is bent beyond the permitted limit, the shielding may suffer displacement, braid opening, or localized fatigue. This risk increases in congested passages, panel entrances, and installations with limited space for accommodation.
Physical separation between power cables and signal cables also deserves attention. Shielding does not replace a well-designed installation route. Prolonged proximity to high-current conductors, busbars, inverters, and noise sources can exceed the rejection capacity of the assembly, especially when there are grounding or termination faults.
Harsh environment and material degradation
Humidity, salt spray, hydrocarbons, chemicals, and temperature variations accelerate degradation processes. Water ingress through poorly sealed ends can reach the shielding and cause corrosion, altering its electrical continuity. In offshore, naval , mining, and oil and gas installations, this risk needs to be addressed from the cable construction selection to the sealing of boxes, connectors, and cable glands.
In mobile applications, the combination of vibration and bending is equally critical. A braided shield, for example, needs to maintain electrical performance without compromising the mechanical strength required by the duty cycle. This is why cables for robotics , conveyors, lifting, and mobile equipment require specific construction, validated for the expected movement regime.
Signs that help locate the problem.
The investigation should begin with the symptoms, but progress to measurements and inspection. Some recurring signs deserve attention:
- Noise or oscillation in 4-20 mA loops and low voltage signals;
- Intermittent communication failures that increase with engine start-up;
- Alarms in encoders, servos, sensors, and instruments with no apparent defect in the device;
- visible heating, corrosion, crushing or breakage near the terminations;
- Difference in behavior between equipment that is stationary and equipment that is in dynamic operation.
Visual inspection is only the first step. Shielding continuity must be verified between the intended connection points, while insulation and conductor integrity require circuit-specific testing. In installations with complex interference, analysis may include noise measurements, grounding assessment, routing inspection, and comparison with up-to-date electrical diagrams.
How to prevent failures from the specification stage onwards.
Prevention starts with complete application information. Simply stating the number of ways and nominal cross-section is not enough. The supplier needs to know the type of equipment connected, the nature of the signal, the presence of inverters, the route, the environment, chemical exposure, bending requirements, and applicable standards.
During the design phase, it's crucial to clearly define where the shielding will be connected, which accessories will maintain metallic continuity, and how power, control, and data segregation will be achieved. EMC cable glands, appropriate connectors, and panels with well-executed equipotential bonding are part of the solution. A technically correct cable can fail if the surrounding elements do not maintain their function.
It is also recommended to establish acceptance and installation criteria. Verifying identification, construction, technical documentation, bending radius, tensile strength, and end integrity reduces rework before the cable goes into operation. For special projects, on-demand manufacturing allows for adjusting materials, shielding, sheathing, and regulatory requirements to the actual usage scenario.
When to replace the cable and when to correct the installation.
Not every incident requires immediate cable replacement. If analysis proves that the fault is limited to the termination, the cable gland connection, or the installation route, a controlled repair may restore performance. This depends on there being no compromise to the shielding along the route, the insulation, or the conductors.
Replacement is indicated when there is internal corrosion, bending fatigue, significant mechanical deformation, loss of continuity in inaccessible sections, or constructive incompatibility with the application. Maintaining an unsuitable cable in a critical operation usually transfers the cost to maintenance, availability, and process safety.
For applications that cannot tolerate instability, the decision must be based on engineering evidence, not trial and error. Innovcable develops special cables focusing on electrical performance, operational resistance, and project suitability, because reliability is not added at the end of the installation: it needs to be defined in the cable, in the assembly, and in the control of every detail in the field.
Failure in Shielded Cables and How to Prevent It
Related Articles

Everything about concentric cable: standards and applications.
Concentric Cable: A Complete Technical Guide for Engineers and Installers. Concentric cable represents an advanced engineering solution for networks.

Trends in Industrial Cables for 2026
Trends in industrial cabling combine automation, data, safety, and durability. Learn how to specify solutions for critical field environments.

Cable selection for frequency inverter
Selecting the right cable for your inverter reduces faults, noise, and downtime. Learn about the electrical, construction, and regulatory criteria for a safe specification.

Critical Safety: When to Specify a High-Performance vs. Conventional Fire Cable
In life safety systems, such as fire detection and alarm systems, the cable specification
Knowledge Academy: Technical information, standards and applications

Tables and Codes for Thermocouples
International Color Code for Compensation and Extension Cables and Wires - Cable Code - Error Limit Table

NBR 5410 Sizing Tables
DOWNLOAD NBR 5410 DIMENSIONING TABLES Explanation With the aim of offering a practical tool to assist in the work of

Color code tables
Color code according to DIN 47100 No. Colour Short Form 1 WHITE WH 2 BROWN BN 3

TABLE AND GUIDELINES AWG X METRIC CONVERSION (mm²)
Unveiling the AWG Standard: A Technical Guide for Professionals and Enthusiasts – American Wire Gauge (AWG) to Metric (mm²) Conversion
Questions? Send a message to the expert.
Access to cutting-edge scientific information is the fuel for innovation. These are the databases, journals, and repositories that our R&D team uses to stay at the forefront of global technical and scientific knowledge.
Databases, Repositories and Search Engines:
- IEEE Xplore Digital Library: The most crucial digital library for electrical and computer engineering. IEEE
- ACM Digital Library: A reference for the field of computer science and information technology. ACM
- Science Direct: Extensive collection of scientific publications and books from the publisher Elsevier. SCIENCE DIRECT
- Scopus: The largest database of abstracts and citations from peer-reviewed literature. scopus
- CAPES Journal Portal: It provides access to international scientific output for the teaching and research community in Brazil. CAPES
- Google Scholar Search tool focused on academic literature. GOOGLE SCHOLAR
- Brazilian Digital Library of Theses and Dissertations (BDTD): Repository of scientific output from Brazilian teaching and research institutions. BDTD
- Directory of Open Access Journals (DOAJ): A directory of high-quality open access journals. DOAJ
Prominent Scientific Periodicals and Journals:
- Naval, Offshore and Petroleum Engineering:
- Ocean Engineering (Elsevier)
- Journal of Ship Research (SNAME)
- Journal of Petroleum Science and Engineering (Elsevier)
- Journal of Marine Science and Engineering (MDPI)
- Journal of the Brazilian Society of Naval Engineering (SOBENA)
- Electrical, Electronic and Telecommunications Engineering:
Products

Profibus DP DeepSea® Armed SHF2
Busbar cable; PROFIBUS DP; Fixed installation; Nominal characteristic impedance: 150 Ω; 1x2x0,64; SHF2; Flame retardant: IEC 60332-1-2; violet; 8 mm

MariTimus® Single-Core Marine Power and Control Cable 0,6/1 kV XLPE/SHF1 (LSOH) Armored and Flame Retardant
Maritimus® Single-Core Naval Power and Control Cable; Armored; Max. 300,00 mm²; 0,6/1 kV; 1 conductor; XLPE / SHF1; Flame Retardant; +90°C; IEC 60092

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Fire Resistant IEC 60331
Maritimus® Single-Core Marine Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Armored and Fire Resistant IEC 60331
Maritimus® Armored Multicore Naval Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331