Power cable for frequency inverter; 0,6/1 kV; 4 conductors; Max. 95,00 mm²; XLPE / PVC; 90°C

Shielded Mobile Use Cable for Control/Command/Power Frequency Inverter InnoDrive® Servo 2XSL(ST)CY-J EMV

Rodent protection?

Provides extra protection against rodents and termites. The price will be updated in your cart.

💡 Add to cart — Immediate purchase. The discount for your volume bracket is automatically applied, and you complete the order online.
📋 Add to quote request Our team will analyze and get back to you with a proposal. Ideal for large volumes, special deadlines, or when you need to add cables that are not available for sale online.

Boost Your Motors with the INNODRIVE SERVO 2XSL(ST)CY-J EMV CableDesigned for connecting drive systems with frequency inverters, this cable ensures maximum efficiency and fault-free power transmission. Its robust construction and high-quality materials guarantee superior performance, protecting your investment and optimizing the operation of your machines. Ensure the strength and precision your industrial system demands.
  • Superior Shielding (EMV): Double shielding protects against electromagnetic interference, ensuring a clean signal and continuous operation.
  • Energy Efficiency: Its low capacitance allows for greater distances between the motor and inverter, with less power loss.
  • High Thermal Performance: XLPE insulation withstands temperatures up to 90°C, allowing for greater current capacity.
  • Versatile Applications: Ideal for installation in dry, humid, or wet environments, offering flexibility for your plant.
  • Reliable Construction: Highly resistant to oils and chemicals, ensuring a long and trouble-free service life.
PRODUCT DESIGN
  • Conductor material: bare copper wires
  • Conductor class: according to IEC 60228 cl. 5
  • Vein isolation: XLPE
  • Vein identification: according to DIN VDE 0293-308, veins stained with GNGE.
  • Stringing: twisted layers of strings
  • Overall shielding: aluminum-laminated polyester tape, metallic side facing outwards, 100% coverage under tinned copper mesh.
  • Outer cover material: PVC
  • Cover color: transparent
  • Rated voltage: Uo/U 0,6/1 kV
  • Test voltage: 4 kV
  • Insulation resistance: min. 200 MΩ x km
  • Operating temperature (fixed): -40°C / +90°C
  • Operating temperature (mobile): -5°C / +90°C
  • Conductor temperature: max. +90°C (in operation); +250°C (in case of short circuit)
  • Flame-retardant properties: self-extinguishing and flame-retardant according to IEC 60332-1
  • Characteristics: low operating capacity, low coupling impedance.
  • Features: Enables interference-free operation of frequency converters through optimized shielding compliant with EMV standards.
DETAILS

Benefits

  • Operation without interference: Optimized double shielding ensures EMC compliance and allows for trouble-free operation of frequency converters.
  • Longer cable length: The low operating capacitance allows for greater distances between the motor and the frequency converter.
  • High-power transmission: It allows for the transmission of higher power with the same conductor cross-section compared to standard versions.
  • Chemical resistance: Highly resistant to acids, bases, and certain types of oils, ensuring durability in industrial environments.
  • High operating temperature: The XLPE conductor insulation allows for a maximum operating temperature of +90°C.
  • Low fire risk: Self-extinguishing and flame retardant material in accordance with IEC 60332-1.
  • Secure installation: Nominal voltage of 0,6/1 kV for greater reliability in drive systems.
  • High Quality Materials: Bare copper conductors conforming to IEC 60228 class 5 for excellent flexibility.
  • Compliance and safety: Produced without silicone, in compliance with RoHS and the EU Low Voltage Directive.
  • Installation flexibility: Suitable for fixed applications and for occasional, free movement.

Applications

  • Drive systems: Power, control and connection cable for systems with frequency converter technology.
  • Industrial automation: Ideal for use in production lines, connecting motors and frequency inverters.
  • Machinery industry: Motor connections in machine tools and processing equipment.
  • Internal facilities: Suitable for installation in dry, damp, and wet locations.
  • Control panels: Used as a connecting cable in control and power distribution panels.
  • Conveyor belt systems: Power supply for motors in transportation and logistics systems.
  • Pumps and fans: Connection of variable speed drives for flow and pressure control.
  • HVAC equipment: Power supply for motors in heating, ventilation and air conditioning systems.
  • Packaging machines: For drives that require precise speed and torque control.
  • Engineering projects: A versatile solution for various engineering applications requiring a shielded cable.
TECHNICAL DATA
General information
BrandINNODRIVE
Product typePower, control and connection cable for drive systems with variable frequency drive (VFD) technology, with low capacitance and double shielding for EMV compliance.
Electrical Parameters
Nominal VoltageUo/U: 0,6/1 kV
Maximum Operating VoltageSingle-phase and three-phase: 700/1200 V; Direct current: 900/1800 V
Test Voltage4 kV
Insulation ResistanceMinimum 200 MΩ x km
CapacitanceLow operating capacitance, allowing for longer cable lengths between the motor and inverter.
Coupling ResistanceLow coupling resistance for optimal electromagnetic compatibility (EMV).
Product Design
Conductor MaterialBare copper wires.
Driver ClassAccording to IEC 60228 class 5.
Vein Isolation MaterialCross-linked polyethylene (XLPE).
Road IdentificationColored wires according to DIN VDE 0293-308, with green-yellow protective conductor (GN/GE).
Type of TwistTwisted veins in layers.
shieldingDouble shielding: Polyester foil laminated with aluminum (100% coverage) and tin-plated copper mesh on top.
Exterior Roofing MaterialPVC compound.
Cover ColorTransparent.
Product characteristics
Application AreaFixed installation and applications with occasional, free movement, without traction effort. Suitable for dry, damp, and wet environments. Not suitable for direct burial.
Silicone-freeYes, during production.
Minimum Radius of Curvature (Fixed)Ø ≤ 12mm: 5 xd; Ø ≤ 20mm: 7.5 xd; Ø > 20mm: 10 xd
Minimum Radius of Curvature (Mobile)Ø ≤ 12mm: 10 xd; Ø ≤ 20mm: 15 xd; Ø > 20mm: 20 xd
Temperature, fixed installation-40 °C to +90 °C.
Temperature, constant movement-5 °C to +90 °C.
Maximum temperature in the driver+90 °C (in operation); +250 °C (in case of short circuit).
Flame retardantSelf-extinguishing and flame retardant according to IEC 60332-1.
UV resistantNot specified for the transparent version.
Chemical resistantHighly resistant to specified acids, bases, and oils.
Applicable Standards
ConformityRoHS, Low Voltage Directive 2014/35/EU, CE.
PatternsIEC 60228 cl. 5, DIN VDE 0293-308, IEC 60332-1.
DIMENSIONAL TABLE
Training nx mm²External Diameter (mm)Weight (kg/km)Current Capacity (A)Capacitance Conductor/Conductor (nF/km)
Capacitance Conductor/Shield (nF/km)
4G 1,510,92122370110
4G 2,5122703280130
4G 413,33624290150
4G 615,258254110170
4G 101879475120190
4G 1621,41.188,00100130220
4G 2525,91.713,00127145230
4G 3529,12.402,00158150260
4G 5033,82.718,00192175290
4G 7038,73.636,00246180300
4G 9542,94.700,00298195320
RELATED PRODUCTS

SHIPPING AND DELIVERY TIMES

Shipping and Delivery Times – FAQ

Q: How does product shipping work?

A: We ship throughout Brazil. We work with the Post Office (SEDEX and PAC) and several partner carriers. When you finalize your purchase, our system calculates and presents the best shipping options available for your zip code, based on the weight and dimensions of your order.

Q: What is the delivery time for my order?

A: Our total delivery time is the sum of two stages: Availability Time + Carrier Time.

  • Availability Period:

    • Products in Stock: If the product is in stock, it will be shipped within 2 business days.

    • Products Made to Order: To ensure maximum quality and flexibility, many of our cables are made to order . In these cases, the production and shipping time is 15 business days.

  • Carrier's deadline:

    • This is the time it takes for the shipping to reach you after we dispatch it. This timeframe is shown when calculating shipping costs in your shopping cart.

Therefore, for a product that is in production, the total estimated delivery time will be 15 business days plus the shipping time.

Q: Why the 15 business day production lead time? What if there are delays?

A: Our on-demand production model allows us to offer superior industrial-quality cables, in the exact length you need, and at extremely competitive prices. As a manufacturing unit, our production process involves several variables, such as receiving raw materials and operating complex machinery. We understand that unforeseen events can occur. Should any event arise that could impact the 15-business-day timeframe, our team will proactively contact you to keep you informed of the new schedule. We are committed to complete transparency throughout the entire process.

Q: Can I cancel an order that is already in production?

A: For products manufactured on demand (make-to-order model), we do not accept cancellations once the order enters our production line. This is because, to ensure speed and competitive pricing, the raw materials for your cable are separated and allocated, and the manufacturing process begins immediately after payment confirmation. Please review your order carefully before finalizing it. If you have any questions, please contact our team.

Shipping Costs

Q: How is the shipping cost calculated?

A: The value is automatically calculated in your shopping cart, based on the total weight of the products, the dimensions of the packaging, and the destination zip code entered.

Q: Do you offer free shipping?

A: We don't currently have a fixed free shipping policy. Occasionally, we may run specific promotions. The most accurate way to check the cost for your location is to add the desired products and your zip code to your cart.

Warranty and Returns

Q: What is the return and exchange policy?

A: According to our policy and the Consumer Protection Code, we accept returns due to buyer's remorse or manufacturing defects within 7 (seven) calendar days of receiving the product. To initiate the process, please contact our Customer Service Center via email. ecommerce@innovcable. Com.br Please provide the order number and reason for the return. The product must be returned in its original packaging, undamaged and showing no signs of misuse. We emphasize that this return policy remains valid and unchanged after receipt.

Q: Do the products have a warranty?

A: Yes. All cables in our product line are guaranteed against manufacturing defects. The specific warranty period can be found on each product page. The warranty does not cover damage caused by incorrect installation, misuse, or natural wear and tear from use.

Loading and Transportation

1. When lifting with a crane, the correct rope must be used, attached to an axle located in the center of the coil.

* Heads up:
– Move it as close to the ground as possible.
Move slowly and, once in the correct position, do not stop abruptly.


2- In the case of a forklift, the drums must not be damaged by the forklift.

* Heads up:
Place the coil in the center of the fork.
The width of the fork must be greater than the spool.

Transportation and unloading

✽ Precautions when handling cables:
• Do not cover the coils.
• Do not roll more than 20 m.
• Do not use sharp objects when moving.
• Do not roll a damaged coil.
• Do not roll on uneven surfaces.
• Do not store the coil near heaters or flammable materials.
 

Checks when handling cables – Storage

• Do not remove the protective materials and packaging that protect the reels and cables until they are used.
• Store in a protected or enclosed location to protect against damage from machinery.
• Store in a suitable, closed storage location for extended periods. (Coils and packaging should be kept in a dry place.)
• Seal both ends of the remaining cables on the reels using heat-shrink tubing to prevent moisture absorption.