TECHNICAL ARTICLES

An unscheduled shutdown due to interconnection failure rarely begins at the moment of rupture. Generally, it is preceded by overheating, loss of insulation, mechanical fatigue, or chemical degradation that progress unnoticed. Knowing when to replace industrial cables is therefore a matter of maintenance, safety, and operational continuity – not just a material replacement.
In critical applications, the cable is an integral part of the system's performance. It conducts power, control signals, data, and instrumentation under conditions that may include continuous bending, twisting, abrasion, oil, moisture, UV radiation, high temperature, electromagnetic interference, and contact with chemical agents. When the specification does not match the actual operating conditions, the service life decreases even if the conductor appears to be in good external condition.
When to replace industrial cables in practice
There is no single replacement schedule that applies to all cables. A fixed circuit installed in a controlled indoor environment can operate for many years without needing replacement. However, a cable for cable carriers, robotics, lifting, or continuous motion systems must be monitored for cycles, bending radius, acceleration, traction, and environmental exposure.
Replacement should be scheduled when inspection indicates a loss of electrical, mechanical, or functional integrity. Waiting for a complete circuit interruption transforms a planned maintenance item into an operational incident, with downtime costs, rework, and risks to the safety of people and assets.
In production lines, naval systems, mining, oil and gas, airports, and power plants, the criticality of the circuit also defines when to replace it. A cable that serves a redundant signal may allow for a wider evaluation window. An emergency stop cable, process control cable, motor drive cable, or safety instrumentation cable requires more conservative criteria.
Signs that require inspection and possible replacement.
Visual inspection is necessary, but not sufficient. Many failures begin internally, due to partial cable rupture, moisture migration, damage to the shielding, or changes in the insulation properties. Even so, some signs in the field require immediate maintenance action:
- Cracks, dryness, hardening, blisters, or discoloration of the coating;
- Cuts, crushing, intense abrasion, and deformations caused by inadequate fastening;
- Exposing shielding, filling, internal insulation, or conductors;
- Abnormal heating at terminals, splices, or cable sections;
- Intermittent failures, alarms without apparent cause, loss of communication or signal variation;
- reduction of insulation resistance, current leakage or recurring activation of protection devices;
- The presence of oil, solvents, water, salinity, or contaminants incompatible with the coating compound.
In cables subjected to movement, the point of greatest concern is usually near connectors, cable glands, panel entries, and areas of repetitive bending. It is common to find an apparently preserved covering while the conductors already show internal fatigue. Therefore, intermittent failures during movement are a relevant indicator, especially in machines with tracks, robots, gantries, and lifting systems.
Essays that support the decision to switch.
Technical assessment should combine operational history, inspection, and measurement. Insulation resistance helps identify degradation due to humidity, temperature, or aging of the insulating material. Continuity and electrical resistance tests of the conductor reveal degraded connections and partial breaks. In shielded cables , the continuity of the shielding and the quality of the grounding should also be verified.
Thermography is especially useful in power circuits. Hot spots can indicate poor contact, inadequate sizing, oxidation, overload, or increased resistance at terminals. The cable is not always the source of the heating, but its continuous exposure to a temperature above the thermal class accelerates insulation degradation.
For control, data, and instrumentation cables, process oscillations, noise in analog signals, communication failures, and erratic inverter behavior may indicate problems with shielding, grounding, circuit segregation, or inadequate construction. Replacing the cable without investigating the cause may only postpone the recurrence of the failure.
In applications with continuous motion , cycle control is crucial. Service life must be monitored according to the actual installation profile: travel, speed, acceleration, bending radius, suspended weight, conveyor orientation, and tensile stress. A cable designed for continuous bending will not deliver the expected performance if installed with a radius smaller than recommended or subjected to unforeseen torsion.
The environment determines the cable's lifespan.
The same construction does not meet all industrial scenarios. In outdoor areas, UV radiation, rain, and temperature variations require weather-resistant materials. In naval or offshore environments , salinity, oil, vibration, and requirements for low smoke and toxic gas emissions may determine cable selection. In mining, abrasion, particulates, and mechanical impact increase the demands on the sheathing.
In installations with frequency inverters, the choice should consider peak voltage, switching frequency, electromagnetic compatibility, and grounding. Conventional cables may exhibit premature insulation deterioration or promote interference in automation systems when used outside of their intended purpose.
There is also the chemical effect. Mineral oils, cutting fluids, fuels, solvents, and cleaning products attack compounds in different ways. A PVC, special rubber, polyurethane, or halogen-free material covering should be chosen according to the agent present, the temperature, and the contact time. The replacement should correct this incompatibility, and not just replace meter by meter with the same unsuitable cable.
Replacing it with an equivalent product isn't always the best decision.
The replacement must preserve, at a minimum, the electrical, mechanical, environmental, and regulatory characteristics of the application. Gauge, nominal voltage, number of conductors, and conductor type are only part of the specification. Flexibility class, shielding, insulation and sheathing material, flame retardancy, oil resistance, thermal range, minimum bending radius, and low smoke or halogen-free requirements must also be evaluated.
In a motion system, for example, a static cable of the same cross-section may conduct the necessary current but fail quickly due to fatigue. In an instrumentation loop, a cable without adequate shielding may maintain electrical continuity and still compromise signal reliability. In a power route with an inverter, a solution without proper construction can increase noise and reduce the lifespan of the motor-cable assembly.
When failures recur, the analysis should consider the entire installation: cable tray sizing, terminal crimping, torque, cable glands, strain relief, power and signal separation, grounding, and routing. Many premature replacements are a consequence of improper assembly, not manufacturing defects.
How to structure an efficient preventive maintenance plan
Maintenance becomes more predictable when cables are classified by criticality and service condition. Safety circuits, continuous production, process control, and essential drives must have clear identification, inspection records, and defined intervention criteria. For mobile assets, recording cycles and occurrences allows for proactive replacement before breakage.
It is recommended to document the type of cable installed, batch number, date of commissioning, environment, electrical parameters, and interventions performed. This history allows for comparison of expected lifespan with actual lifespan and identification of patterns, such as failures concentrated in a machine, on a specific route, or under a particular process condition.
Innovcable develops special cables considering the actual conditions of use, with solutions for control, instrumentation, conveyors, robotics, lifting, servomotors, frequency inverters, and demanding environments. In non-standard projects, applied engineering allows for the adaptation of materials, construction, and performance to operational needs.
The best time to replace a cable is not after a failure. It's when inspection data, tests, and process behavior show that reliability is no longer assured. Transforming these signals into a technical decision protects the operation and gives the system the continuity it was designed to deliver.
When to safely replace industrial cables
Related Articles

Everything about concentric cable: standards and applications.
Concentric Cable: A Complete Technical Guide for Engineers and Installers. Concentric cable represents an advanced engineering solution for networks.

Trends in Industrial Cables for 2026
Trends in industrial cabling combine automation, data, safety, and durability. Learn how to specify solutions for critical field environments.

Cable selection for frequency inverter
Selecting the right cable for your inverter reduces faults, noise, and downtime. Learn about the electrical, construction, and regulatory criteria for a safe specification.

Critical Safety: When to Specify a High-Performance vs. Conventional Fire Cable
In life safety systems, such as fire detection and alarm systems, the cable specification
Knowledge Academy: Technical information, standards and applications

Tables and Codes for Thermocouples
International Color Code for Compensation and Extension Cables and Wires - Cable Code - Error Limit Table

NBR 5410 Sizing Tables
DOWNLOAD NBR 5410 DIMENSIONING TABLES Explanation With the aim of offering a practical tool to assist in the work of

Color code tables
Color code according to DIN 47100 No. Colour Short Form 1 WHITE WH 2 BROWN BN 3

TABLE AND GUIDELINES AWG X METRIC CONVERSION (mm²)
Unveiling the AWG Standard: A Technical Guide for Professionals and Enthusiasts – American Wire Gauge (AWG) to Metric (mm²) Conversion
Questions? Send a message to the expert.
Access to cutting-edge scientific information is the fuel for innovation. These are the databases, journals, and repositories that our R&D team uses to stay at the forefront of global technical and scientific knowledge.
Databases, Repositories and Search Engines:
- IEEE Xplore Digital Library: The most crucial digital library for electrical and computer engineering. IEEE
- ACM Digital Library: A reference for the field of computer science and information technology. ACM
- Science Direct: Extensive collection of scientific publications and books from the publisher Elsevier. SCIENCE DIRECT
- Scopus: The largest database of abstracts and citations from peer-reviewed literature. scopus
- CAPES Journal Portal: It provides access to international scientific output for the teaching and research community in Brazil. CAPES
- Google Scholar Search tool focused on academic literature. GOOGLE SCHOLAR
- Brazilian Digital Library of Theses and Dissertations (BDTD): Repository of scientific output from Brazilian teaching and research institutions. BDTD
- Directory of Open Access Journals (DOAJ): A directory of high-quality open access journals. DOAJ
Prominent Scientific Periodicals and Journals:
- Naval, Offshore and Petroleum Engineering:
- Ocean Engineering (Elsevier)
- Journal of Ship Research (SNAME)
- Journal of Petroleum Science and Engineering (Elsevier)
- Journal of Marine Science and Engineering (MDPI)
- Journal of the Brazilian Society of Naval Engineering (SOBENA)
- Electrical, Electronic and Telecommunications Engineering:
Products

Profibus DP DeepSea® Armed SHF2
Busbar cable; PROFIBUS DP; Fixed installation; Nominal characteristic impedance: 150 Ω; 1x2x0,64; SHF2; Flame retardant: IEC 60332-1-2; violet; 8 mm

MariTimus® Single-Core Marine Power and Control Cable 0,6/1 kV XLPE/SHF1 (LSOH) Armored and Flame Retardant
Maritimus® Single-Core Naval Power and Control Cable; Armored; Max. 300,00 mm²; 0,6/1 kV; 1 conductor; XLPE / SHF1; Flame Retardant; +90°C; IEC 60092

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Fire Resistant IEC 60331
Maritimus® Single-Core Marine Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331

MariTimus® Marine Single-Core Power and Control Cable 0,6/1 kV MICA / XLPE / SHF1 (LSOH) Armored and Fire Resistant IEC 60331
Maritimus® Armored Multicore Naval Power and Control Cable; Max. 120,00 mm²; 0,6/1 kV; 1 conductor; MICA / XLPE / SHF1; Fire Resistant; +90°C; IEC 60092; 60331