• Standard: BS 7671
  • Table 4D4A
  • Shielded multi-core cables with 70°C thermoplastic insulation.
  • Copper conductors
  • Driver temperature: 70 °C
  • Ambient air temperature: 30 °C
  • Ambient soil temperature: 30 °C
Area
da
section
cross
nominal
do
conductor
[mm²]
Current carrying capacity in [A]
Reference Method C
(Cut directly)
Reference Method E
(outdoors or
in perforated cable tray
horizontal or vertical)
Reference Method F
(directly into the ground or into ducts)
(on the ground, inside or around buildings)
1 two-phase cable
CA or CC
1 three-phase cable
or 1 four-phase cable
CA
1 two-phase cable
CA or CC
1 three-phase cable
or 1 four-phase cable
CA
1 two-phase cable
CA or CC
1 three-phase cable
or 1 four-phase cable
CA
123456
1234567
1.5211822192218
2.5282531262924
4383341353730
6494253454638
106758726260507
16897797837864
251181021281109982
3514512515713511998
50175151190163140116
70222192241207173143
95269231291251204169
120310267336290231192
150356306386332261217
185405348439378292243
240476409516445336280
300547469592510379316
400621540683590