• Standard: BS 7671
  • Table 4E1A
  • Single-core, unarmored, 90°C thermoset insulated cables, with or without shielding.
  • Copper conductors
  • Driver temperature: 90 °C
  • Ambient temperature: 30°C
Area
da
section
cross
nominal
do
conductor
[mm²]
Current carrying capacity in [A]
Reference Method A
(enclosed in conduit)
on the wall
with thermal insulation etc.)
Reference Method B
(enclosed in conduit)
on a wall or in
channel, etc.)
Reference Method C
(Cut directly)
Reference Method F
(outdoors or in a horizontal or vertical perforated cable tray)
PlayingSpaced
by a diameter
2 cables,
monophase
CA or CC
3 or 4
ropes,
Three-phase AC
2 cables,
monophase
CA or CC
3 or 4
ropes,
Three-phase AC
2 cables,
monophase
CA or CC
3 or 4
ropes,
Three-phase AC
2 cables,
monophase
CA or CC
map
3 cables,
three-phase AC
map
3 cables,
Three-phase AC
Clover
2 single-phase cables
AC or DC or 3 cables
three-phase AC flat
HorizontalVertical
1234567891011
123456789101112
1141317151917.5
1.5191723202523
2.5262331283431
4353142374641
6454054485954
10615475668174
1681731008810999
2510695133117143130161141135182161
35131117164144176161200176169226201
50158141198175228209242216207275246
70200179253222293268310279268353318
95241216306269355326377342328430389
120278249354312413379437400383500454
150318285393342476436504464444577527
185362324449384545500575533510661605
240424380528450644590679634607781719
300486435603514743681783736703902833
400 68358486879394086882310851008
500 783666990904108399894612531169
630 9007641130103312541151108814541362
800 1288117913581275121415811485
1000 1443132315201436134917751671