• Standard: BS 7671
  • Table 4E2A
  • Thermoset insulated multi-core cables (90°C) with thermoplastic sheathing, unarmored.
  • Copper conductors
  • Driver temperature: 90 °C
  • Ambient temperature: 30°C

 

Area
da
section
cross
nominal
do
conductor
[mm²]
Current carrying capacity in [A]
Reference Method A
(enclosed in conduit)
on the wall
with thermal insulation etc.)
Reference Method B
(enclosed in conduit)
on a wall or in
channel, etc.)
Reference Method C
(Cut directly)
Reference Method E
(outdoors or
in perforated cable tray
horizontal or vertical)
1 two-phase cable
CA or CC
1 three-phase cable
or 1 four-phase cable
CA
1 two-phase cable
CA or CC
1 three-phase cable
or 1 four-phase cable
CA
1 two-phase cable
CA or CC
1 three-phase cable
or 1 four-phase cable
CA
1 two-phase cable
CA or CC
1 three-phase cable
or 1 four-phase cable
CA
12345678
123456789
114.513171519172118
1.518.516.52219.524222623
2.52522302633303632
43330403545404942
64238514458526354
105751696080718675
167668918010796115100
259989119105138119149127
35121109146128171147185158
50145130175154209179225192
70183164221194269229289246
95220197265233328278352298
120253227305268382322410346
150290259334300441371473399
185329295384340506424542456
240386346459398599500641538
300442396532455693576741621
400 625536803667865741