• Standard: BS 7671
  • Table 4E4A
  • Thermosetting insulated multi-core cables, shielded, 90°C
  • Copper conductors
  • Driver temperature: 90 °C
  • Ambient air temperature: 30 °C
  • Ambient soil temperature: 30 °C
Area
da
section
cross
nominal
do
conductor
[mm²]
Current carrying capacity in [A]
Reference Method C
(Cut directly)
Reference Method E
(outdoors or
in perforated cable tray
horizontal or vertical)
Reference Method F
(directly into the ground or into ducts)
(on the ground, inside or around buildings)
1 two-phase cable
CA or CC
1 three-phase cable
or 1 four-phase cable
CA
1 two-phase cable
CA or CC
1 three-phase cable
or 1 four-phase cable
CA
1 two-phase cable
CA or CC
1 three-phase cable
or 1 four-phase cable
CA
123456
1234567
1.5272329252521
2.5363139333328
4494252444336
6625366565344
10857390787158
1611094115999175
2514612415213111696
35180154188162139115
50219187228197164135
70279238291251203167
95338289354304239197
120392335410353271223
150451386472406306251
185515441539463343281
300698599732628446365
400787673847728