• Standard: BS 7671
  • Table 4H1A
  • Single-core thermoplastic insulated cables, 70°C, unarmored, with or without shielding.
  • Aluminum conductors
  • Driver temperature: 70 °C
  • Ambient temperature: 30°C
Area
da
section
cross
nominal
do
conductor
[mm²]
Current carrying capacity in [A]
Reference Method A
(enclosed in conduit)
on the wall
with thermal insulation etc.)
Reference Method B
(enclosed in conduit)
on a wall or in
channel, etc.)
Reference Method C
(Cut directly)
Reference Method F
(outdoors or in a horizontal or vertical perforated cable tray)
PlayingSpaced
by a diameter
2 cables,
monophase
CA or CC
3 or 4
ropes,
Three-phase AC
2 cables,
monophase
CA or CC
3 or 4
ropes,
Three-phase AC
2 cables,
monophase
CA or CC
3 or 4
ropes,
Three-phase AC
2 cables,
monophase
CA or CC
map
3 cables,
three-phase AC
map
3 cables,
Three-phase AC
Clover
2 single-phase cables
AC or DC or 3 cables
three-phase AC flat
HorizontalVertical
1234567891011
123456789101112
509384118104125110149133128169152
70118107150133160140192173166217196
95142129181161195170235212203265241
120164149210186226197273247237308282
150189170234204261227316287274356327
185215194266230298259363330316407376
240252227312269352305430392375482447
300289261358306406351497455434557519
380 413352511472543502507625584
480 477405591546629582590726680
600 545462679626722669680837787
740 771709820761776956902
960 90082395388690711251066
1200 10229261073999102612931229