• Standard: BS 7671
  • Table 4H3A
  • Single-core, shielded, thermoplastic insulated cables with corrosion resistance up to 70°C.
  • Aluminum conductors
  • Driver temperature: 70 °C
  • Ambient temperature: 30°C
Area
da
section
cross
nominal
do
conductor
[mm²]
Current carrying capacity in [A]
Reference Method C
(cut directly)
Reference Method F
(outdoors or in a horizontal or vertical perforated cable tray)
PlayingPlayingSpaced by a cable diameter
2 cables,
monophase
CA or CC plan
3 or 4
ropes,
three-phase AC flat cable
2 cables,
monophase
CA or CC plan
3 cables,
three-phase AC flat
3 cables,
three-phase AC trefoil
2 DC cables2 AC cables
single-phase AC
3 or 4 cables
Three-phase AC
HorizontalVerticalHorizontalVerticalHorizontalVertical
12345678 9 10 11
123456789101112
50143133152141131167157168159169155
70183168194178168214202212200213196
95221202234214205261247259245255236
120255233270246238303288299285293272
150294267310282275349333340323335312
185334303352319315400382389371379354
240393354413374372472452457437443415
300452405474427430545523520498505475
380518452543479497638613583559551518
480586501616534568742715655629604568
600658550692589642859828724696656618
740728596769642715986952802770707666
96081965186870680811711133866832770726
120089369295275688013601317938902822774