• Standard: BS 7671
  • Table 4J1A
  • Single-core, unarmored, 90°C thermoset insulated cables, with or without shielding.
  • Aluminum conductors
  • Driver temperature: 90 °C
  • Ambient temperature: 30°C
Area
da
section
cross
nominal
do
conductor
[mm²]
Current carrying capacity in [A]
Reference Method A
(enclosed in conduit)
in a wall with thermal insulation
etc.).
Reference Method B
(enclosed in conduit)
on a wall or in
channel, etc.)
Reference Method C
(Cut directly)
Reference Method F
(outdoors or in a horizontal or vertical perforated cable tray)
PlayingSpaced
by a diameter
2 cables,
monophase
CA or CC
3 or 4
ropes,
Three-phase AC
2 cables,
monophase
CA or CC
3 or 4
ropes,
Three-phase AC
2 cables,
monophase
CA or CC
3 or 4
ropes,
Three-phase AC
2 cables,
monophase
CA or CC
map
3 cables,
three-phase AC
map
3 cables,
Three-phase AC
Clover
2 single-phase cables
AC or DC or 3 cables
three-phase AC flat
HorizontalVertical
1234567891011
123456789101112
50125113157140154136184165159210188
70158142200179198174237215206271244
95191171242217242211289264253332300
120220197281251280245337308296387351
150253226307267324283389358343448408
185288256351300371323447413395515470
240338300412351439382530492471611561
300387344471402508440613571544708652
380 658594679628638798742
480 765692786728743927865
600 8717919038368491058990
740 1001911102595197912181143
960 1176107211911108115114401355
1200 1333121713411249130716431550