Voltage drop (in ampere-meters):

Conductor operating temperature: 90°C

Area
da
section
cross
do
conductor
1 dual-core cable or 2 single-core cables
DC
Dual-core cable, single-phase alternating current.1 cable with three, four or five cores, three-phase AC.2 single-core cables in contact
single-phase AC*
12346
(mm2)(mV/A/m)(mV/A/m)(mV/A/m)(mV/A/m)
413.213.211.1
68.58.57.4
105.15.14.4
163.23.22.7
  rxzrxzrxz
252.032.030.1752.041.730.151.73
351.42 1.220.151.231.440.211.46
501.00 0.910.1450.931.000.211.02
700.71 0.620.140.640.710.200.73
950.54 0.470.1350.490.540.1950.57
1200.42 0.370.1350.390.420.1900.46
1500.34 0.290.1300.320.340.1900.39
1850.27 0.240.1300.270.270.1900.33
2400.21 0.1880.1300.230.210.1850.28
3000.167 0.1470.1250.1950.1730.1800.25
4000.127 0.1320.1750.22
5000.100 0.1070.1700.20
6300.074 0.0850.1700.190

Remarks:

The voltage drop values ​​provided above are based on a conductor operating temperature of 90°C and are therefore not accurate when the operating temperature exceeds 90°C. In the case of 180°C cables with a conductor temperature of 150°C, the resistive values ​​above should be increased by a factor of 1,2.
A greater voltage drop will occur if the cables are spaced further apart.